Basler Electric DGC-2020ES User Manual

Page 144

Advertising
background image

136

9469200990 Rev C

Name

Description

Symbol

RDPPROGPREALM1

When true, this element illuminates the Battery Overvoltage
LED on the Remote Display Panel RDP-110.

When this

element is connected in logic, it overrides all other
commands to the LED. Otherwise, the LED operates as
normal.

RDPPROGPREALM2

When true, this element illuminates the Battery Charger
Failure
LED on the Remote Display Panel RDP-110.

When

this element is connected in logic, it overrides all other
commands to the LED. Otherwise, the LED operates as
normal.

RESET

Reset will be active when this element is true. Reset can
also be accomplished by pressing the Reset button on the
front panel of the DGC-2020ES.

RUNINHIBIT

When this logic element is true, the DGC-2020ES is
prevented from starting and running the generator,
regardless of any condition that would normally cause the
generator to run. If this element is false and there is any
condition in effect which will cause the generator to run, the
DGC-2020ES will start and run the generator.

RUNMODE

When this input is true, and the DGC-2020ES is in OFF
mode, the DGC-2020ES will switch to RUN mode. This is a
pulsed input. It does not need to be held after the desired
mode switch has occurred.

RUNOUTPUT

This element is used to drive the run output relay from logic
when the Run Output Relay configuration is set to
“Programmable”. When the Run Output Relay configuration
is set to “Programmable”, the run relay will not close unless
logic is used to drive this element. When the Run Output
Relay configuration is set to “Predefined”, the run relay is
closed according to the predefined run functionality of the
DGC-2020ES. When the “Predefined” functionality is
selected, the relay will not respond to this element.

RUNWLOAD

The Start input starts the generator and closes the Gen
breaker. The Stop input stops the generator and opens the
Gen breaker. The DGC-2020ES only responds to this logic
element when in AUTO mode.

SPEEDLOWER

This element lowers the speed setting of the DGC-2020ES
by up to 2 rpm per second. After the speed has not been
lowered for 30 seconds, the modified speed is saved to
nonvolatile memory.

SPEEDRAISE

This element raises the speed setting of the DGC-2020ES
by up to 2 rpm per second. After the speed has not been
raised for 30 seconds, the modified speed is saved to
nonvolatile memory.

STARTDELBYP

This element allows the Pre Start state to be skipped based
on logic. For example, a start delay may not be necessary
when the engine is warm. This also allows an external
device, such as an ECU, to control the pre start interval.

BESTlogic

Plus

DGC-2020ES

Advertising