9469200990 Rev C

155

Rated Volts (V L-L)

This setting accepts values from 1 to 99,999, in increments of 1.

Rated Power Factor (PF)

This setting accepts values from -1 to 1, in increments of 0.001.

Genset kW Rating

This setting accepts values from 5 to 9,999, in increments of 1.

Rated Engine RPM

This setting accepts values from 750 to 3,600, in increments of 1.

Calculated Rated Data

Rated Secondary Volts, Rated Phase Amps, Rated Secondary Phase Amps, Rated kVA, and Rated kvar
are calculated automatically. The equations used for these calculations are listed below.





=

Volts

Primary

PT

Gen

Volts

Secondary

PT

Gen

Volts

Rated

Volts

Secondary

Rated

Error! Bookmark not defined.

3

Volts

L

L

Rated

kVA

Rated

machine)

phase

(3

Amps

Phase

Rated

=

Volts

L

L

Rated

kVA

Rated

machine)

phase

(1

Amps

Phase

Rated

=





=

Amps

Primary

CT

Amps

Secondary

CT

Amps

Phase

Rated

Amps

Phase

Secondary

Rated

PF

Rated

kW

Rated

kVA

Rated

=

2

PF

Rated

1

kVA

Rated

kvar

Rated

=

Frequency

The frequency settings allow selection of the rated frequency of the generator and an alternate frequency.

Rated Frequency of the Unit

Rated frequency settings consist of 50 and 60 Hz.

Alternate Frequency

This setting accepts values from 10 to 450, in increments of 0.01.

Battery Volts

The nominal voltage of the starter battery is used by the DGC-2020ES to detect and annunciate battery
overvoltage and low or weak battery voltage. The Battery Volts settings consist of 12 V and 24 V.

Generator Connection

Genset connection types accommodated by the DGC-2020ES include three, three-phase connections
(delta, wye, and grounded delta) and a single-phase configuration (sensing across phases A and B.)

DGC-2020ES