Basler Electric DGC-2020ES User Manual

Page 201

Advertising
background image

9469200990 Rev C

193

Notes

1.

If the CEM-2020 is providing one end of the J1939 bus, a 120

Ω,

½ watt terminating resistor should be installed across terminals
P1- LO (CANL) and P1- HI (CANH).

2.

If the CEM-2020 is not part of the J1939 bus, the stub connecting
the CEM-2020 to the bus should not exceed 914 mm (3 ft) in
length.

3.

The maximum bus length, not including stubs, is 40 m (131 ft).

4.

The J1939 drain (shield) should be grounded at one point only. If
grounded elsewhere, do not connect the drain to the CEM-2020.

Figure 92. CAN Interface with CEM-2020 providing One End of the Bus

Figure 93. CAN Interface with DGC-2020ES providing One End of the Bus

DGC-2020ES

CEM-2020

(Optional)

P0067-96

Engine

120 ohm

Termination

CAN-H

CAN-L

Other

Devices

120 ohm

Termination

Bus

Stub

DGC-2020ES

Other

Devices

P0067-85

Engine

120 ohm

Termination

CAN-H

CAN-L

CEM-2020

(Optional)

120 ohm

Termination

Bus

Stub

DGC-2020ES

CEM-2020

Advertising