Basler Electric DGC-2020ES User Manual

Page 141

Advertising
background image

9469200990 Rev C

133

Name

Description

Symbol

LOADTAKEOVER

When this logic element is true, the generator is forced to
start, assume load, and disconnect from the mains, in an
open transition.

LOGICALM

When this input is true, the DGC-2020ES goes into an
alarm condition.

LOGICPALM

When this input is true, the DGC-2020ES goes into a Pre-
alarm condition.

LOWFUELPALM

When this element is true, a Low Fuel Pre-Alarm is
annunciated and the Low Fuel Level LED on the RDP-110
is illuminated.

MAINSFAILTEST

When this element is true, the DGC-2020ES will exercise its
mains fail transfer function exactly as it would if the mains
were to fail on a mains fail machine.

This can be used as a

test of the mains fail transfer capability of the unit without
having to cause a true mains failure.

MAINSFLTRINHIBIT

The mains fail transfer function is inhibited when the Set
input is true.

DGC-2020ES

BESTlogic

Plus