Basler Electric DGC-2020ES User Manual

Page 134

Advertising
background image

126

9469200990 Rev C

Name

Description

Symbol

MPU Fail

True when the MPU has failed.

Oil Pressure
Sender Fail

True when the Oil Pressure Sender Fail is configured
as a pre-alarm and the activation delay has expired.

Voltage Sensing
Fail

True when the Voltage Sensing Fail is configured as a
pre-alarm and the activation delay has expired.

Weak Battery

True when the Weak Battery Voltage Pre-Alarm
settings have been exceeded.

Senders

Coolant Temp
Sender Fail

True when the Coolant Temp Sender Fail is configured
as either a pre-alarm or alarm and the activation delay
has expired.

Fuel Level
Sender Fail

True when the Fuel Level Sender Fail is configured as
either a pre-alarm or alarm and the activation delay
has expired.

Oil Pressure
Sender Fail

True when the Oil Pressure Sender Fail is configured
as either a pre-alarm or alarm and the activation delay
has expired.

Speed Sender
Fail

True when the Speed Sender Fail activation delay has
expired.

Voltage Sensing
Fail

True when the Voltage Sensing Fail is configured as
either a pre-alarm or alarm and the activation delay
has expired.

Logic Control Relays

The logic control relays (LCR) consist of LCR outputs and LCR inputs. The output can be used to terminate the
“output” end of a logic network, and then use the corresponding input as an input to logic elsewhere in the logic
scheme. When a given LCR output is true the corresponding LCR input is true. In other words, when LCR Output
N (N being a number from 1 to 16) becomes true, then LCR Input N is true also.
If you get a “too many logic levels” error while building a logic network, LCR outputs and inputs can be used as a
solution to this problem. Place an LCR output on the end of the partial logic network and then use the
corresponding LCR input to build more logic than was previously possible.

Inputs
Input 1-16

See description above.

Outputs
Output 1-16

See description above.

Components

This group contains Logic Gates, Pickup and Dropout Timers, Latches, and Comment Blocks. Table 24
lists the names and descriptions of the objects in the Components group.

BESTlogic

Plus

DGC-2020ES

Advertising