Basler Electric DGC-2020ES User Manual

Page 132

Advertising
background image

124

9469200990 Rev C

Name

Description

Symbol

DPF
Regenerate
Required

True when the Diesel Particulate Filter (DPF) lamp
status broadcast over CAN Bus indicates that DPF
regeneration is required.

DPF Soot Level
High

True when the engine ECU reports via CAN Bus that
Diesel Particulate Filter (DPF) soot level is high.

DPF Soot Level
Moderately High

True when Diesel Particulate Filter (DPF) lamp status
(yellow warning) broadcast over CAN Bus indicates
that the soot level is moderately high.

DPF Soot Level
Severely High

True when Diesel Particulate Filter (DPF) lamp status
(red warning) broadcast over CAN Bus indicates that
the soot level is severely high.

ECU Comm
Loss

True when communication to ECU has been lost.

Fuel Leak

True when the Fuel Leak Detect function is configured
as a pre-alarm and the activation delay has expired.

Fuel Level
Sender Fail

True when the Fuel Level Sender Fail is configured as
a pre-alarm and the activation delay has expired.

Generator
Breaker Close
Fail

True when a generator breaker close fail pre-alarm
occurs. The pre-alarm occurs when the DGC-2020ES
has issued a generator breaker close output but does
not receive a generator breaker status input that
indicates the breaker has closed before the breaker
close wait time has expired.

Generator
Breaker Open
Fail

True when a generator breaker open fail pre-alarm
occurs. The pre-alarm occurs when the DGC-2020ES
has issued a generator breaker open output but does
not receive a generator breaker status input that
indicates the breaker has opened before the breaker
close wait time has expired.

Generator
Protection
27

True when the 27 element is configured as a pre-alarm
and has tripped.

Generator
Protection
59

True when the 59 element is configured as a pre-alarm
and has tripped.

Generator
Protection
47

True when the 47 element is configured as a pre-alarm
and has tripped.

Generator
Protection
50

True when the 50 element is configured as a pre-alarm
and has tripped.

Generator
Protection
81 Over

True when the 81 Over element is configured as a pre-
alarm and has tripped.

Generator
Protection
81 Under

True when the 81 Under element is configured as a
pre-alarm and has tripped.

Global Pre-
Alarm

True when one or more pre-alarms are set.

BESTlogic

Plus

DGC-2020ES