Contact sensing, Engine system inputs – Basler Electric DGC-2020ES User Manual

Page 184

Advertising
background image

176

9469200990 Rev C

Bus Sensing
Configuration .................................... Line-to-line
Bus Sensing Terminals .................... 46 (A-phase)
(Optional with style number xx2)

48 (B-phase)

50 (C-phase)

Contact Sensing

Contact sensing inputs include seven programmable inputs. All inputs accept dry contacts.

Time from a DGC-2020ES input application to:

Shutdown the generator via an alarm = 490 ms max

Close a relay on board the DGC-2020ES = 215 ms max

Close a relay on board the CEM-2020 = 400 ms max

Notes

A contact input is true (on) if the input is connected to battery ground
with a resistance of less than 240 ohms.

The maximum length of wire that can be accommodated depends on
the resistance of the wire, and the resistance of the contacts of the
device driving the input at the far end of the wire.

The maximum wire length can be calculated as follows:

L

max

= (240

– R

device

)/(Resistance per Foot of Desired Wire)

Terminals

Input 1 .............................................. 3, 17
Input 2 .............................................. 4, 17
Input 3 .............................................. 5, 17
Input 4 .............................................. 6, 17
Input 5 .............................................. 7, 17
Input 6 .............................................. 8, 17
Input 7 .............................................. 9, 17

Engine System Inputs

Stated accuracies are subject to the accuracy of the senders used. Values within these ranges are
deemed “good” and the DGC-2020ES will use them for the appropriate calculation and protection. Values
outside these ranges are deemed “bad” and the DGC-2020ES will begin timing towards a sender failure
condition.

Fuel Level Sensing

Resistance Range ............................ 5 to 250

Ω nominal

Terminals.......................................... 1, 2 (sender common)

Coolant Temperature Sensing

Resistance Range ............................ 5 to 2,750

Ω nominal

Terminals.......................................... 53, 2 (sender common)

Oil Pressure Sensing

Resistance Range ............................ 5 to 250

Ω nominal

Terminals.......................................... 52, 2 (sender common)

Specifications

DGC-2020ES