Ne872a distribution monitor and control module, Overview – GE Industrial Solutions Pulsar Plus Controller User Manual
Page 100
Pulsar Plus Controller Family
Issue 7 December 2011
100
Following is a summary of the parts utilized in the 1-Wire management system
Probe And Cable Descriptions
Comcode
QS873A battery thermal probe
108987611
10-ft Probe to Infinity NE interconnect
848719795
5-ft Probe to probe interconnect
848719803
10-ft Probe to probe interconnect
848719811
ES771A Voltage Monitoring Module
108958422
2.5-ft Probe to ES771A interconnect
CC848791517
10-ft Probe to ES771A interconnect
848719829
4-ft ES771A to ES771A/Infinity NE interconnect
CC848791500
10-ft ES771A to ES771A/Infinity NE interconnect
848652947
NE872A Distribution Monitor and Control Module
Overview
The NE872A (CC109124780) allows the Pulsar Plus family of controllers to manage various distributions
through serial communications in rectifier and converter based systems. The system controller will
communicate over the GP RS485 bus to the NE872A and monitor associated alarms for open load or battery
protectors, measure a single shunt configured as a load or battery shunt, monitor the DC bus voltage for
back-up LVD functionality, and control and monitor a single load or battery latching LVD contactor. The
board allows addressing for up to eight NE872As being installed in a system. Figure 17 shows the
connections and interfaces for the NE872A.