100

Following is a summary of the parts utilized in the 1-Wire management system

Probe And Cable Descriptions

Comcode

QS873A battery thermal probe

108987611

10-ft Probe to Infinity NE interconnect

848719795

5-ft Probe to probe interconnect

848719803

10-ft Probe to probe interconnect

848719811

ES771A Voltage Monitoring Module

108958422

2.5-ft Probe to ES771A interconnect

CC848791517

10-ft Probe to ES771A interconnect

848719829

4-ft ES771A to ES771A/Infinity NE interconnect

CC848791500

10-ft ES771A to ES771A/Infinity NE interconnect

848652947

NE872A Distribution Monitor and Control Module

Overview

The NE872A (CC109124780) allows the Pulsar Plus family of controllers to manage various distributions
through serial communications in rectifier and converter based systems. The system controller will
communicate over the GP RS485 bus to the NE872A and monitor associated alarms for open load or battery
protectors, measure a single shunt configured as a load or battery shunt, monitor the DC bus voltage for
back-up LVD functionality, and control and monitor a single load or battery latching LVD contactor. The
board allows addressing for up to eight NE872As being installed in a system. Figure 17 shows the
connections and interfaces for the NE872A.