GE Industrial Solutions Pulsar Plus Controller User Manual

Page 144

Advertising
background image

Pulsar Plus Controller Family

Issue 7 December 2011

144

Table 51 T1.317 Alarms With No Threshold Related Command

obj,attr

Description

sta

cha

ope

type

Range of Values

objid,ide

Identifier

text

see below

objid,des

Description

text

see below

objid,fds

Front Panel Description

text

see below

objid,ast

Alarm state

number 0=not active 1=active

objid,sev

Alarm severity

text

CRIT, MAJ, MIN, WRN, RO

objid,led

LED

text

BD,AC,DC,””

objid,acc

Contact Closure

text

R1,R2,R3,R4,R5,R6,R7,””

objid,dly

Notify Delay

number 0-540 seconds

objid,noo

Notify On Occur

number 0=no 1=yes

objid,nor

Notify On Retire

number 0=no 1=yes

objid,nag

NAG On Occur

number 0=no 1=yes

objid,dst

Notify Destination

text

“”, P1, P2, P3, P4, E1, E2, E3, E4,
S1, S2, S3, S4

obj

Description

aac1

ACO Active

acf1

AC fail

amj1

Auxiliary Fuse Major

ata1

Alarm Test Active

atb1

Alarm Test Aborted

aux1

Auxiliary alarm 1

aux2

Auxiliary alarm 2

aux3

Auxiliary alarm 3

aux4

Auxiliary alarm 4

aux5

Auxiliary alarm 5

aux6

Auxiliary alarm 6

bbl1

Memory Backup Battery Low

bfa1

Battery Test Failed

bta1

Battery test active

cch1

Configuration Changed

cdid1

Converter ID Conflict

cfa1

Converter Fail

clc1

Clock Changed

clm1

Rectifier Current Limit

cma1

Minor Communication Fail Alarm

cnf1

LVBD 1 Failed

cnf2

LVLD 1 Failed

cnf3

LVLD 2 Failed

cnf4

LVLD 3 Failed

cno1

LVBD 1 Open

cno2

LVLD 1 Open

cno3

LVLD 2 Open

cno4

LVLD 3 Open

cof1

Queue Overflow

cor1

Number Did Not Respond

did1

ID Conflict

epo1

Emergency power (battery) off

epr1

External Password Reset

exl1

Excessive Login Attempts

faj1

External 24V Fuse Major

Advertising