GE Industrial Solutions Pulsar Plus Controller User Manual

Page 59

Advertising
background image

Pulsar Plus Controller Family

Issue 7 December 2011

59

Table 10 Status LEDs - Custom Assignable - Phoenix

4

LED

5

Color

Alarm Name

Condition

ACF

Amber AC Fail Alarm

A rectifier is reporting AC failure.

RFA

Amber

Rectifier Fail
Alarm

A rectifier has failed.

RFAM

(MRFA)

Red

Rectifier Fail
Multiple Alarm

Multiple rectifiers have failed.

HVSD

Red

High Voltage
Shutdown Alarm

One or more rectifiers is shutdown due to plant voltage
exceeding the configured threshold.

HVA

Red

High Voltage
Alarm

System voltage exceeds the configured threshold.

BOD
(BD)

Red

Battery on
Discharge Alarm

System voltage below configured threshold.

VLV

(LLVA)

Red

Very Low Voltage
Alarm

System voltage below configured threshold.

(USR2)

Amber

User configurable LED.

Advertising