GE Industrial Solutions Pulsar Plus Controller User Manual
Page 59
Advertising
Pulsar Plus Controller Family
Issue 7 December 2011
59
Table 10 Status LEDs - Custom Assignable - Phoenix
4
LED
5
Color
Alarm Name
Condition
ACF
Amber AC Fail Alarm
A rectifier is reporting AC failure.
RFA
Amber
Rectifier Fail
Alarm
A rectifier has failed.
RFAM
(MRFA)
Red
Rectifier Fail
Multiple Alarm
Multiple rectifiers have failed.
HVSD
Red
High Voltage
Shutdown Alarm
One or more rectifiers is shutdown due to plant voltage
exceeding the configured threshold.
HVA
Red
High Voltage
Alarm
System voltage exceeds the configured threshold.
BOD
(BD)
Red
Battery on
Discharge Alarm
System voltage below configured threshold.
VLV
(LLVA)
Red
Very Low Voltage
Alarm
System voltage below configured threshold.
(USR2)
Amber
User configurable LED.
Advertising