Pulsar Plus Controller Family

Issue 7 December 2011

58

Table 9 Status LEDs - Dedicated - Phoenix

LED

2

Color

Alarm Name

Condition

SYSOK

3

(NORM)

Green System OK

System OK - Normal operation, no alarms, inputs and
outputs are in their normal range.

PMN

3

Amber Minor Alarm

Medium severity - Generally assigned to alarms which
indicate a non-power affecting condition. Attention
eventually required.

PMJ

3

Red

Major Alarm

High severity - Generally assigned to alarms which indicate
a power affecting condition. Immediate attention required.

PCR

3

Red

Critical Alarm

Highest severity - Generally assigned to alarms which
indicate a power affecting condition. Immediate attention
required.

FLOAT

Green Float Mode

One or more of the following alarms are present: Fuse
Minor 48, Fuse Minor 24

EQL

Amber

Equalize / Boost
Mode

One or more of the following alarms are present: Open
String, LVBD Open, Fuse Major 48, Fuse Major 24

Table 10 Status LEDs - Custom Assignable - Phoenix

4

LED

5

Color

Alarm Name

Condition

TCA

Amber

Total Current
Alarm

Plant load current exceeds configured distribution current
rating.

TCOMP

(TEMP COMP)

Amber

Temperature
Compensation
Active

System voltage has been increased or decreased by the
configured Temperature Compensation feature.

BAT

Amber

Battery
Temperature
Alarm

Battery temperature is above the configured threshold.

DCA

Amber

Distribution
Current Alarm

Distribution branch current exceeds the configured
threshold.

CFA

Red

Converter Fail
Alarm

A DC/DC converter has failed.

DFA

(FAJ)

Red

Distribution Fuse
Alarm

A distribution or battery fuses or circuit breakers is open.

LVD

Red

Low Voltage
Disconnect
Alarm

A battery contactor is open due to plant voltage lower than
the configured threshold.

(USR1)

Amber

User configurable LED.

TEMP

Amber

Temperature
Alarm

Ambient temperature is not within configured thresholds.

LMR

Amber

Limited Recharge
Alarm

Load current exceeds the configured % of rectifier capacity
during normal operation.
Alternatively, when load exceeds that of a configured
number of redundant rectifiers.

2

LED labels in parentheses indicate alternate designations not printed on the display label.

3

The highest severity in the system will take precedence.

4

LED labels are printed on the Front Panel. When custom assigned, place an appropriate label over the printed LED

designation.

5

LED labels in parentheses indicate alternate designations not printed on the Front Panel.