Table 5 output alarm connector – GE Industrial Solutions Pulsar Plus Controller User Manual

Page 34

Advertising
background image

Pulsar Plus Controller Family

Issue 7 December 2011

34

Connect to the Controller

Step

Action

Table 5 Output Alarm Connector

Pin #
Wire

Color

Signal
Name

Pin #
Wire

Color

Signal
Name

Pulsar Plus Display

Defaults

Phoenix Display

Defaults

1

(BL)

PCR

11

(BL-BK)

PCR_C

Power Critical Alarm

(PCR)

2

(O)

PMJ

12

(O-BK)

PMJ_C

Power Major Alarm

(PMJ)

3

(G)

PMN

13

(G-BK)

PMN_C

Power Minor Alarm

(PMN)

4

(BR)

R1

14

(W-BK)

R1_C

Battery on Discharge

(BD)

AC/Multiple AC Fail

(ACF, MACF)

5

(S)

R2

15

(BK-W)

R2_C

AC/Multiple AC Fail

(ACF/MACF)

Battery on Discharge,

Battery Test Active

(BD, BTA)

6

(BL)

R3

16

(BL-R)

R3_C

Rectifier/Converter Fail

(RFA/MRFA,

CFA/MCFA)

Distribution Fuse/CB Alarm,

Open String

(FAJ1/2, FAN1/2, CDFA, AMJ,

OSA)

7

(O)

R4

17

(R)

R4_C

Very Low Voltage

(VLV)

High Voltage

(HVA, HFV)

8

(G)

R5

18

(R-G)

R5_C

Fuse Alarm - 48V

2

(External FAJ2/FAN2)

Rectifier Fail,

Incompatible Rectifier

(RFA, RFN, ICR)

9

(BR)

R6

19

(R-W)

R6_C

High Voltage

(HV)

Multiple Rectifier Fail

(MRFA)

10

(S)

R7

20

(R-BK)

R7_C

Fuse Alarm - 24V

2

(External FAJ1/FAN1)

Converter Fail/Multiple

Converter Fail, Converter

Redundancy Loss, Converter

Low Voltage, Converter High

Voltage, Converter ID Conflict

(CFA, MCFA, CFN, CRL, CVLA,

CHVA, CHFV, CDID)


1 Configuration jumpers for the alarm outputs have been set to provide an “Open” on alarm

from the factory. See previous sections for changing the alarm contact type at J4.

2 Depending on the system rectifier voltage one of these will be defaulted as a general purpose

output User Relay. Ex: if the system is -48V, then User relay R7 is unassigned and vice versa.