Pulsar Plus Controller Family

Issue 7 December 2011

95

VT-Probe Connect to Controller

Step

Action

3

Insert the 3-pin connector end of the cable into the receptacle on the VT-Probe closest to the
controller.


4

Snap the cover closed on the VT-probe.

5

Place the first probe to the negative battery post as shown in figure.

6

The controller automatically recognizes the VT-probes. The number of registered temperature
probes and the highest battery temperature monitored may be checked from the front panel
by scrolling down the menu at MenuStatusBatteries. The fields are “Num Temp Probes
()” and Highest Temp () where () contains the number of devices communicating in the system
as well as the highest battery temperature.

7

Connect either the 848719803 (5-ft) or the 848719811 (10-ft) cable to the 2-position
receptacle of the first probe and to the 3-position receptacle of another probe.

Verify the number of probes (2) registered with the controller with command:
MenuStatusBatteriesNUM TEMP PROBES (2)