Table d-1 standard configuration item defaults – GE Industrial Solutions Pulsar Plus Controller User Manual

Page 177

Advertising
background image

Pulsar Plus Controller Family

Issue 7 December 2011

177

Table D-1 Standard Configuration Item Defaults

Factory Default

Factory 24V

Rectifier

Default

Factory 48V

Rectifier

Default

Category

Description

Range

Factory

Factory 24V

Factory 48V

obj,attr

Battery 25 Type

"TEL12-105F"

BT25,BTY

Battery 25 Class

"VALVE-REG"

BT25,BTC

Battery 25 Capacity

100

BT25,CAP

Batteries

Number Of Battery Strings

0 to 16 Strings

0

DC1,NST

Battery Model

≤ 14 Characters

"Valve-Reg"

DC1,BTY

Battery

Discharge Test

Timed Test Duration

0:0:0 to 23:59:59

4:00:00

BR1,TMD

Automatic Battery Test Feature

disabled, 20%, timed

"disabled"

BR1,BTE

Automatic Test (AT) Interval

1 to 18 Months

12

BR1,TIN

Date For Next Automatic Test

yyyy-mm-dd

1/1/2099

BR1,ATD

Start Time For Automatic Test

0 to 23

0

BR1,ATH

Hours To Wait From Last BD Before
AT

0 to 240 hours

72

BR1,ATW

Manual Test Type

disabled, 20%, timed

"disabled"

BR1,MTT

Reserve Time Low (Full Capacity)

0.0 to 99.9 hours

0

RTL1,THR

Real-time Reserve Low (During BD)

0.0 to 99.9 hours

0

RRTL1,THR

Battery Sections

String 1 contactor

CN1 to CN4

"DCN01"

B01,CON

String 1 Number of strings

1 to 70

0

B01,NST

String 1 Battery type

"VALVE-REG"

B01,BTY

String 2 contactor

CN1 to CN4

"DCN01"

B02,CON

String 2 Number of strings

1 to 70

0

B02,NST

String 2 Battery type

"VALVE-REG"

B02,BTY

String 3 contactor

CN1 to CN4

"DCN01"

B03,CON

String 3 Number of strings

1 to 70

0

B03,NST

String 3 Battery type

"VALVE-REG"

B03,BTY

Battery Boost

Boost Maximum Duration

1 to 80 Hours

1

BS1,TMD

Automatic Boost Feature

disabled, timed, or

current

"disabled"

BS1,ATM

Auto Boost BD Multiplication Factor

0.1 to 9.0

0.5

BS1,AMF

Auto Boost Termination Current
Threshold

1 to 999A

5

BS1,CTA

Shunt Monitors

Plant Shunt Type

Battery/None /Load

"BATTERY"

DCMC1,TYP

Plant Shunt Current Rating

0 to 9999 Amps

600

DCMC1,SHA

ID1 Type

Battery/None /Load

"BATTERY"

DCM01,TYP

ID1 Shunt Current Rating

0 to 9999 Amps

300

DCM01,SHA

ID2 Type

Battery/None /Load

"NONE"

DCM02,TYP

ID2 Shunt Current Rating

0 to 9999 Amps

300

DCM02,SHA

ID3 Type

Battery/None /Load

"NONE"

DCM03,TYP

ID3 Shunt Current Rating

0 to 9999 Amps

600

DCM03,SHA

ID4 Type

Battery/None /Load

"NONE"

DCM04,TYP

ID4 Shunt Current Rating

0 to 9999 Amps

600

DCM04,SHA

ID5 Type

Battery/None /Load

"NONE"

DCM05,TYP

ID5 Shunt Current Rating

0 to 9999 Amps

600

DCM05,SHA

ID6 Type

Battery/None /Load

"NONE"

DCM06,TYP

ID6 Shunt Current Rating

0 to 9999 Amps

600

DCM06,SHA

Advertising