Pulsar Plus Controller Family

Issue 7 December 2011

112

Table 41 ES772 Connector J1 Pinout Definitions

Pin

Name

Definition

Comments/Connections

1

VPWR +

V(+) Power

Power for ES772A, connect to VBus(+)

2

N/A

Reserved

3

N/A

Reserved

4

SHUNT-

Neg Batt Shunt Input

Polarity is during battery discharge

5

BATT1_SENSE

Polarity Sense for String 1

Connect to battery negative, V(-) of String 1

6

DIST_ALM_1

Trip-Indicator Input-1 for US
Style CB or GMT Fuse. Alarm
on closure to VBus(-).

Connect to NC terminal of breaker micro switch or to
indicator lead of GMT fuse, other end (C) referenced to
VBus(-).

7

EXT BAT SW1

Alarm input for external
battery disconnect switch;
alarm on closure to VBus(-).

Connect to NC micro switch of US Style CB, other end
(C) referenced to VBus(-), micro switch must close upon
manual opening of CB.

8

VPWR -

V(-) Power

Power for ES772A, connect to VBus(-)

9

STATUS1_RTN

Reference for STATUS1

Connect to C pin of micro switch of Contactor 1.

10 STATUS1

Contactor 1 Status Monitor

Connect to NO pin of micro switch of Contactor 1.

11 SHUNT+

Positive Battery Shunt Input

Polarity is during battery discharge

12 LVD1_COIL

Contactor 1 coil input

Connect to one side of Contactor 1 coil, other side of
coil connected to VBus(+).

13 DIST_ALM_2

Trip-Indicator Input-2 for US
Style CB or GMT Fuse. Alarm
on closure to VBus(-).

Connect to NC terminal of breaker micro switch or to
indicator lead of GMT fuse, other end (C) referenced to
VBus(-).

14 EXT BAT SW2

Alarm input for external
battery disconnect switch;
alarms on closure to VBus(-).

Connect to NC micro switch of US Style CB, other end
(C) referenced to VBus(-), micro switch must close upon
manual opening of CB.

Table 42 ES772 Connector J3 Pin Definitions

Pin

Name

Definition

Comments

1

BATT2_SENSE

Polarity Sense for String 2.

Connect to battery negative VBus(-) of string 2.

2

STATUS2_RTN

Reference for STATUS2.

Connect to C pin of micro switch of Contactor 2.

3

STATUS2

Contactor 2 Status Monitor.

Connect to NO pin of micro switch of Contactor 2.

4

LVD2_COIL

Contactor 2 coil input.

Connect to one side of Contactor 2 coil, other side of
coil connected to VBus(+).

Figure 22: Typical Alarm Connections