Auxiliary port connector, J100 and j101 serial ports, Table 43 auxiliary port connector signals – GE Industrial Solutions Pulsar Plus Controller User Manual

Page 115

Advertising
background image

Pulsar Plus Controller Family

Issue 7 December 2011

115

Auxiliary Port Connector

Table 43 Auxiliary Port Connector Signals

Pin

Function

Pin

Function

1

DIN CB-1

2

DIN CB-2

3

DIN CB-3

4

DIN CB-4

5

DIN CB-5

6

DIN CB-6

7

DIN CB-7

8

DIN CB-8

9

DIN CB-9

10

DIN CB-10

11

EXT AUX MAJ-1

12

EXT AUX MAJ-2

Figure 25: Alarm Connections for DIN Style Load Protectors

Figure 25 shows the connections required if load protectors are the DIN style circuit breakers. Note that 10
alarm inputs are provided for monitoring up to 10 DIN breakers because these breakers must be monitored
individually. The DIN CB(1-10) inputs are alarmed on an open to VBus(-).

J100 and J101 Serial Ports
J100 and J101 are used to connect the ES772A to the controller. Note that if QS873A VT-Probes are to be
used in conjunction with the ES772A, connect J100 or J101 on the ES772A to the controller via the Auxiliary
Port connector on the controller, and then connect the QS873A to the unused RJ-45 jack on the ES772A.

If the ES772A is being used with both the QS873A and the ES771A Remote Voltage Monitoring Module,
connect either the ES771A or the QS873A to the controller as both have two RJ-45 jacks for serial
communication purposes. Then connect the two-jack device not connected to the controller to the unused
serial port of the two-jack device connected to the controller, and connect the QS873A to its second serial
port.