Pulsar Plus Controller Family

Issue 7 December 2011

150

Table 63 T1.317 Input Management Related Commands

obj,attr

Description

sta

cha

ope

type

Range of Values

inmnn,stt

Input state

text

0=not alarming 1=alarming

inmnn,typ Input alarm type

text

"" – no alarm, for in006, this value

allows the input to be used
for either group standby or
PBT. Polarity is ignored.

"FAN1" - drives FAN1 alarm
"FAN2" – drives FAN2 alarm
"FAJ1" – drives FAJ1 alarm
"FAJ2" – drives FAJ2 alarm
"OSA1" – drives OSA1 alarm
"AMJ1" – drives AMJ1 alarm, not

valid for NE872 or other LVD
card inputs.

"AUX1" – drives AUX1 alarm
"AUX2" – drives AUX2 alarm
“AUX3" – drives AUX3 alarm
“AUX4" – drives AUX4 alarm
“AUX5" – drives AUX5 alarm
“AUX6" – drives AUX6 alarm
"REMLVD" – Active signal opens

battery contactors for built-in
plant input, or for LVD inputs,
it opens the contactor on the
card where the signal is
active.

inmnn,pol

Input alarming state

text

CLOSED, OPEN


where: m is the distribution interface module ID from 1 to 4

nn is the input number from 01 to the number of inputs supported by the distribution interface

module

Built-in plant inputs

Object

Signal Name

Default Description

In001

FAJ1

Fuse Alarm Major 24V

In002

FAJ2

Fuse Alarm Major 48V

In003

AUX_PMJ

Auxiliary Major Alarm

In004

OS_BATT

Open String

In005

EPO_IN

Emergency Power Off

In006

PBT_IN

Group Standby/PBT

In007

AUX1_IN

Air Conditioner Fail

In008

AUX2_IN

Door Open

In009

AUX3_IN

High External Ambient

In010

AUX4_IN

Low External Ambient

Table 64 T1.317 Call-Out Manager Related Commands

obj,attr

Description

sta

cha

ope

type

Range of Values

cm1,des

Description

text

30 char (Call-Out Manager)

cm1,ngi

NAG Interval

Number 15 to 60 minutes