Pulsar Plus Controller Family

Issue 7 December 2011

125

Environmental Specifications

Item

Specification

Operating Temperature

-40 to 75°C (-40 to 167°F)

Storage Temperature

-40 to 85°C (-40 to 185°F)

Altitude

-200 to 13,000 feet (-61 to 3962 meters)

7

Humidity

10% to 95% non-condensing

Audible Noise

< 60 dBA

Earthquake Rating

Zone 4, upper floors

Controlled Environment

Use this equipment in a controlled environment (an area where the
humidity is maintained at levels that cannot cause condensation on
the equipment, the contaminating dust is controlled, and the steady-
state ambient temperature is within the range specified).

Installation Area Specifications

Item

Specification

Installation Area Limitations

Store and operate this equipment in a controlled environment,
an area where the humidity is maintained at levels that cannot cause
condensation on the equipment, the contaminating dust is controlled,
and the steady-state ambient temperature is within the range
specified.

Operation Without Batteries

Item

Specification

Suitability without Batteries

Suitable for use in power plants with or without batteries.

Loss of AC Power
without Batteries

Loss of ac power causes

• Controller DC power is lost
• Controller alarm relays are activated (unpowered)

Recovery from
Loss of AC Power
without Batteries

Restoration of AC power causes

• Rectifiers return to their configured voltage set point
• Controller DC power is restored
• Controller automatically return to its last configuration

Alarm relays reflect actual alarm states

7

For altitudes above 5000 feet (1524 meters), derate the temperature by 3.6 °F per 1000 feet (0.656 °C per

100 meters).