DISABLEDAuto boost cancelled by being disabled

his

Report BD History

Syntax:

dc1,bod

Description
This command reports the battery discharge history in the following format:
his dc1,bod
30-MAY-03,15:11:12,MANUAL,COMPLETED,118.3,23,
01-APR-03,03:11:12,BD,COMPLETED,118.3,26,130
12-FEB-03,12:00:02,PERIODIC,COMPLETED,120.9,27,135
.
**

This report gives the start date, start time, start reason, current at start of discharge, duration
in minutes, and, if calculated, a reserve time prediction. The start reasons are:

MANUALDischarge test initiated by user
PERIODICPeriodic discharge test
BDNatural battery discharge

The stop reasons are:

COMPLETEDDischarge completed normally
TIMEOUTAuto discharge test timed out
DISABLEDAuto discharge test disabled
ENDVDischarge test hit end voltage
CANCELEDDischarge test canceled by user

lis

List Rectifiers

Syntax:

lis rec

Description
This command is used to list all the rectifiers in the system. The command will list all present
and missing rectifiers. Missing rectifiers are rectifiers that have been removed from a shelf.
The cle will clear missing rectifiers from the controller's memory and they will no longer be
listed by this command. Return value for a system with 3 rectifiers on shelf 1 would look like
the following:

* lis rec
G11
G12
G13
.
* _

login

Log-in

Syntax:

login “password
where password is either the user, super-user or administrator password