Alarm Thresholds

Table 16 Alarm Thresholds Status

Float Voltage Alarms Shows the configured settings for the Float Settings: Very High Major (HVSD),

High Minor, Battery on Discharge (BD) and Very Low Voltage (VLV) alarms.
Values are shown in (xx.xxV) format.

Boost Voltage
Alarms

Shows the configured settings for the Boost Settings: Very High Major (HVSD),
High Minor, and Battery on Discharge (BD) alarms. Values are shown in (xx.xxV)
format.

High Batt Temp

Shows measured value of the highest battery temperature of all attached
QS873 battery thermal probes.

Reserve Low

Shows configured value for the Low battery reserve time alarm.

High Ambient Temp

Shows configured value for the High Ambient Temperature alarm. This
temperature is from the temperature sensor located on the controller itself.

Low Ambient Temp

Shows configured value for the Low Ambient Temperature alarm. This
temperature is from the temperature sensor located on the controller itself.

Enabled/Disabled Info

This section of the menu provides a location to determine the Enable/Disable status of most controller
features.

Table 17 Enabled/Disabled Info Status

Temp Comp

Shows whether Battery Temperature Compensation is Enabled or Disabled.

Low Temp Comp

Shows if the Low Temperature compensation features is Enabled or Disabled.
Note: General temperature compensation must be Enabled to use Low
Temperature compensation.

Recharge Ilim

Shows if the Recharge Current Limit feature is Enabled or Disabled.

Emrgncy Pwr Off

Displays whether or not the Emergency Power Off (Remote Emergency Battery
Disconnect) feature is Enabled or Disabled. If Enabled, EPO is asserted when
contact closure is applied to the EPO input. The controller will keep battery
contactors open until this contact closure has been removed. The feature
assumes that AC has been removed to the system.

Critical=Major

Shows if the assertion of the Critical alarm severity with all Major alarms
feature is Enabled or Disabled.

ACO

Shows if Audible Alarm Cut-off feature is Enabled or Disabled.

Local Buzzer

Shows if the on-board local audible buzzer is Enabled or Disabled.

Alarm Test

Shows if the Form-C Alarm Test Feature is Enabled or Disabled.

Auto Boost

Shows if the automatic boost charge mode of operation is Enabled or Disabled.

Auto Batt Test

Shows if the automatic battery test feature is Enabled or Disabled.

Rect Redundancy

Shows if the Rectifier redundancy feature is Enabled or Disabled.

Mid-Cell V Mon

Shows if the Mid-String Voltage imbalance detection feature is Enabled or
Disabled.

Imminent Shutdn

Shows if the Imminent system shutdown alarm (LVBD) feature is Enabled or
Disabled.