Table 45 Specifications

General Specifications

Item

Specification

Input Voltage Ranges (power)

+/-24 volts: from +/-18 volts to +/-30 volts;
-48 volts: from -36.5 volts to -60 volts SELV

Input Power

6.0 watts maximum

Input Power Connections

NE843A/CP843A/EP843D, No external connection required;
NE843C/NE843E/NE843G/NE843P, (J9)12-pin connector

Bonding Network

Suitable for installation as part of either

• Common Bonding Network (CBN)
• an Isolated Bonding Network (IBN)

Facilities

Suitable for installation in

• Network Telecommunication Facilities
• Locations where the NEC applies

DC Return

Isolated DC Return (DC-I)

or

Common DC Return (DC-C)

Front Panel User Interface

4 or 8-line by 40-character LCD

Severity sensitive backlit LCD
(LEDs on NE 843P);

Three status LEDs (20 on NE843P)

Voltage test jacks;

Six Push Buttons
(Rotary Control + 2 Push Buttons on NE843P)

System Configuration Methods

Front panel LCD display and menu keys

(J5) and (J8) 10/100 Base-T port/s
(J7) DB9 for RS-232 port: T1.317 or EasyView
(J6) RJ11 for phone line connection –MODEM option

Maximum Power Units

60 NE Power Units

32 CP Power Units

Low-Voltage Disconnects

Manage up to eight LVD contactors using up to 3 independent
configurable Load disconnect thresholds (LVLDs) and 1 configurable
Battery disconnect threshold (LVBD).

Temperature Monitoring

Up to 16 One-Wire Battery Temperatures;
One on-board internal ambient temperature