Table d-1 standard configuration item defaults – GE Industrial Solutions Pulsar Plus Controller User Manual

Page 174

Advertising
background image

Pulsar Plus Controller Family

Issue 7 December 2011

174

Table D-1 Standard Configuration Item Defaults

Factory Default

Factory 24V

Rectifier

Default

Factory 48V

Rectifier

Default

Category

Description

Range

Factory

Factory 24V

Factory 48V

obj,attr

Contactor Interfaces

ID1 Type

None/CN1/

CN2/CN3/CN4

"CN1"

DCN01,TYP

ID2 Type

None/CN1/

CN2/CN3/CN4

"CN2"

DCN02,TYP

ID3 Type

None/CN1/

CN2/CN3/CN4

"CN3"

DCN03,TYP

ID4 Type

None/CN1/

CN2/CN3/CN4

"CN4"

DCN04,TYP

ID5 Type

None/CN1/

CN2/CN3/CN4

"None"

DCN05,TYP

ID6 Type

None/CN1/

CN2/CN3/CN4

"None"

DCN06,TYP

ID7 Type

None/CN1/

CN2/CN3/CN4

"None"

DCN07,TYP

ID8 Type

None/CN1/

CN2/CN3/CN4

"None"

DCN08,TYP

Imminent LVBD Shutdown

1=Enabled

0=Disabled

0

DC1,ISD

Rectifiers

Rectifier Redundancy Loss Enable

1=Enabled

0=Disabled

0

GM1,RME

Rectifier Loadshare Enable

1=Enabled

0=Disabled

1

GM1,LSE

Rectifier Float Current Limit

30 to 100%

100

GM1,FCL

Rectifier Boost Current Limit

30 to 100%

100

GM1,BCL

Group Standby/Sequencing Enable

1=Enabled

0=Disabled

0

DC1,RSQ

Remote rectifier Off Enable

1=Enabled

0=Disabled

0

PS1,RRF

Rectifier Redundancy Threshold

1 to 80

1

RLS1,THR

Multiple Rectifier Fail

2 to 88

2

MFA1,THR

Oring FET test enable

1=Enabled

0=Disabled

1

GM1.OFT

Efficiency Enable

1=Enabled

0=Disabled

1

DC!,EME

Efficiency Target

20% to 95%

70

DC1,EMT

Efficiency Rectifier Turn On
Threshold

25% to 100%

76

DC1,EMO

Converters

Converter Internal Selective High
Output Voltage Shutdown

25.0 to 30.0V50.0 to

60.0V

58.0

29.0

CP1,VSD

High Output Voltage Major Alarm

25.0 to 30.0V
50.0 to 60.0V

56.0

28.5

CHVA1, THR

High Output Voltage Minor Alarm

24.0 to 30.0V
48.0 to 60.0V

54.0

27.0

CHFV1,THR

Output Voltage Set-Point

23.0 to 27.2V
46.0 to 54.5V

52.0

26.0

CP1,VSP

Low Voltage Alarm

20.0 to 27.0V
40.0 to 54.0V

46.0

23.0

CVLA1,THR

Converter Current Limit

30 to 100%

100

CP1,CLM

Converter Redundancy Loss Enable

1=Enabled

0=Disabled

0

CP1,RME

Remote converter Off Enable

1=Enabled

0=Disabled

0

CP1,ROF

Low Voltage Disconnect Input
Threshold

20.0 to 25.0V
40.0 to 50.0V

23.0

46.0

CP1,DTH

Low Voltage Reconnect Input
Threshold

22.0 to 27.0V
44.0 to 54.0V

25.0

50.0

CP1,RTH

Low Voltage Disconnect Enable

1=Enabled

0=Disabled

0

CP1,LVD

Converter Redundancy Threshold

1 to 32

1

CRL1,THR

Multiple Converter Fail

2 to 30

2

CMFA1,THR

Battery Type

Definitions

Battery 1 Type Description

<=32 chars

"Generic Valve-Reg

Battery"

BT01,DES

Battery 1 Type

"Valve-Reg"

BT01,BTY

Battery 1 Class

"VALVE-REG"

BT01,BTC

Battery 1 Capacity

0

BT01,CAP

Battery 2 Type Description

<=32 chars

"Generic Flooded Battery"

BT02,DES

Advertising