Table 55 T1.317 DC Converter Related Commands

obj,attr

Description

sta

cha

ope

type

Range of Values

csr,des

Description

Text

DC Converter sr

csr,typ

Type

Text

10 chars

csr,sn

Serial number

Text

Serial number

csr,adc

DC Current

Number Number in amps

csr,cap

Capacity

Number Number in amps

csr,stt

State

Text

ON*, OFF, STANDBY*,
MISSING, VACANT*
ON qualifiers –LIM
OFF qualifiers –LVD, -INF, -
TA, -HVSD, -FAN

csr,cfa

Converter Fail

Number 0=inactive 1=active

csr,did

ID Conflict

Number 0=inactive 1=active

csr,ccf

Communication Fail

Number 0=inactive 1=active

s stands for shelf number (0 or 1)
r stands for converter number (1 thru 6)
* The user may only set the state to ON, STANDBY, or VACANT

Table 56 T1.317 Battery Reserve Management Related Commands

obj,attr

Description

sta

cha

ope

type

Range of Values

br1,des

Description

Text

Battery Reserve 1

br1,adc

Total battery current

number d A (+ for discharge, - for

charge)

br1,hbt

Highest battery temperature

number dd °C

br1,cap

Installed battery capacity

number ddddd AH

br1,olcap

On-line battery capacity

number ddddd AH

br1,btr

Discharge test results

result,reserve,load

text

result is one of the following:
COMPLETED
CHECK BATTERY
INTERRUPTED
ACTIVE
NOT RUN
reserve is hours calculate by
last complete test
load is load at beginning of
test

br1,tth

High Temperature Threshold

Number 30-90

°

C or 86-194

°

C

br1,cle

Current Limit Enable

number 0=disable 1=enable

br1,clt

Current Limit Threshold

number 5-1000A

br1,cev

Battery string end of discharge V

Number 19.25-22.75V

or 40.25-43.75V

br1,bts

Battery Test State

number 0=inactive 1=active

br1,mtt

Manual test type

text

DISABLED, 20%, TIMED

br1,tev

Manual test alarm voltage

number 21-27V or 36-48 V

br1,tmd

Manual test duration

number 0.1-99.9 hours

br1,bte

Auto test type

text

DISABLED, 20%, TIMED

br1,btv

Battery test rectifier voltage

number 21-26 V or 42-52 V

br1,ath

Auto test start hour

number 0-23

br1,tin

Auto test interval

number 1-18 months

br1,atw

Auto test min hours after BD

number 0-240 hours

br1,atd

Auto test date

date

dd-mmm-yy