J100 and j101, Qs871a distribution monitor and control module, Overview – GE Industrial Solutions Pulsar Plus Controller User Manual

Page 105: Module features, Figure 20: qs871a remote distribution module, Table 36 ne872 j100 and j101 signal description

Advertising
background image

Pulsar Plus Controller Family

Issue 7 December 2011

105

J100 and J101
Provides connectivity to the RS485 GP rectifier/converter bus as well as a pass through to the next RS485
connected device.

Table 36 NE872 J100 and J101 Signal Description

Pin #

Signal

Signal Description

1

RS485+

B Inverting Driver Output / Inverting Receiver Input

2

RS485-

A Non-inverting Receiver Input/ Non-inverting Driver Output

3

RS485REF

RS485 Reference/return. Pass-through on this board.

4-8

No Connection

QS871A Distribution Monitor and Control Module

Overview

The QS871A (CC109103371) allows the Pulsar Plus family of controllers to obtain distribution data through
serial communications. The system controller monitor alarms for open load or battery protectors, measures
load or battery shunts, monitors the bus voltage, and controls and monitors a single load or battery LVD
contactor. Figure 20 shows the connections and interfaces for the QS871A.

Figure 20: QS871A Remote Distribution Module

Module Features

The QS871A module has the following features:

Status LED: This is a tri-colored LED and will illuminate accordingly for the conditions shown below.

LEDs ( = On)

Green

Amber

Red

Condition

Normal

Minor Alarm

Major Alarm

Flashing

Communication Loss with Controller

Flash (5s)

Manual Reconnect Command Accepting

In addition, the following alarms will be issued for the conditions noted. This assumes the external
disconnect switch is used to open and close the battery charging path to the batteries.

Condition

Contactor

Fail Alarm

Contactor

Open

Alarm

Open

String

Alarm

Controller

LED

QS871

LED

Open Integral QS871A Disconnect Switch

X

RED

Blinking