Table 53 T1.317 Rectifiers Related Commands

obj,attr

Description

sta

cha

ope

type

Range of Values

gsr,adc

DC Current (VI, VIR)

number number A

gsr,vdc

DC Voltage

number number V

gsr,stt

Individual rectifier state

text

ON*, OFF, STANDBY*,
VACANT*, MISSING

gsr,cap

Capacity

number number A

gsr,tmp

Temperature

number number F or C

gsr,seq

Use In Sequence Enable

number 0=no 1=yes

gsr,rfa

Rectifier Fail

number 0=inactive 1=active

gsr,acf

AC Fail

number 0=inactive 1=active

gsr,man

Standby or Manual Off

number 0=inactive 1=active

gsr,did

ID Conflict

number 0=inactive 1=active

gsr,clm

Current Limit

number 0=inactive 1=active

gsr,rcf

Communication Fail

number 0=inactive 1=active

gsr,rfn

Fan fail

number 0=inactive 1=active

s stands for shelf number (1 to 6)
r stands for rectifier number (1 to 7)
* The user may only set the state to ON, STANDBY, or VACANT

Table 54 T1.317 Converter Plant Related Commands

obj,attr

Description

sta

cha

ope

type

Range of Values

cp1,des

Description

Text

Converter Plant 1

cp1,typ

Converter output type

Text

24V or 48V

cp1,vdc

DC Voltage

Number Number in volts

cp1,adc

DC Current

Number Number in amps

cp1,cap

Installed capacity

Number Number in amps

cp1,olcap

Online capacity

Number Number in amps

cp1,vsp

Voltage Set-Point

Number 23-28V or 46-57V

cp1,vsd

Internal high voltage shutdown

Number 25-30V or 50-60V

cp1,dth

Low Voltage Discon Threshold

Number 20-25V or 40-50V

cp1,rth

Low Voltage Recon Threshold

Number 22-27V or 44-54V

cp1,lvd

Low Voltage Disconnect Enable

Number 0=disabled 1=enabled

cp1,rss

Converter restart

number 1=restart

cp1,rme

Redundancy monitor enable

number 0=disable,1=enable

Cp1,rof

Remote standby enable

number 0=disable,1=enable