Table 47 t1.317 user login related commands, Table 48 t1.317 dc plant related commands – GE Industrial Solutions Pulsar Plus Controller User Manual

Page 142

Advertising
background image

Pulsar Plus Controller Family

Issue 7 December 2011

142

Table 47 T1.317 User Login Related commands

obj,attr

Description

sta

cha ope

type

Range of Values

x,ide

Identifier

text

USR01-USR14, ADM1

x,des

Description

text

User Account 1-14
Administrator Account

x,pwd

Password

text

15 characters

x,usr

User name

text

15 characters

x,lvl

Security level

text

“USER”, “SUPER-USER”,
“ADMINISTRATOR”

Table 48 T1.317 DC Plant Related Commands

obj,attr

description

sta

cha ope

type

Range of Values

dc1,ide

Description

text

DC1

dc1,des

Description

text

DC Plant 1

dc1,typ

Plant Type

number 48V, 24V

dc1,vdc

Plant voltage

number dd.dd V

dc1,adc

Plant load current

number ddd.d A

dc1,cap

Total installed rectifier capacity

number ddd.d A

dc1,olcap

Total on-line rectifier capacity

number ddd.d A

dc1,trd

Plant total rectifier drain

number ddd.d A

dc1,sht

Centralized plant shunt type

Text

“NONE”, ”BATTERY”, ”LOAD”

dc1,sha

Centralized plant shunt size

Number 0=disabled 1-9999

dc1,stt

Plant state

text

“FLOAT”, “BOOST”

dc1,bod

Battery on discharge

number 0=on discharge 1=not on

discharge

dc1,rss

Rectifier restart

number 0=no action 1=restart

dc1,rsq

Rectifier sequencing

number 0=disable 1=enable

dc1,ron

User Group TR request

Number 0-3 LSB = User, MSB=PBT

dc1,rot

All Rectifier On Threshold

number 20-25or 40-50 volts

dc1,nst

Number of battery strings

number 1-70

dc1,cps

Number of Cells per String

number 1-75 (24V plant) or 24 (48V plant)

dc1,bty

Battery type

Text

See battery type definitions
default (OPE causes battery
defaults to be loaded)

dc1,isd

Imminent shutdown enable

number 0=disable 1=enable

dc1,rtm

Actual reserve time

text

Low Current-Batt current too low
High Current-Batt current too high
dd.d (in hours)

dc1,scap

String capacity

number

dc1,mls

All load shunts monitored

number 0=disable 1=enable

Table 49 T1.317 Alarms With Two Thresholds Related Command

obj,attr

Description

sta

cha

ope

type

Range of Values

objid,ide

Identifier

text

see below

objid,des

Description

text

see below

objid,fds

Front Panel Description

text

see below

objid,ast

Alarm state

number 0=not active 1=active

objid,led

LED

text

BD,AC,DC,””

objid,sev

Alarm severity

text

CRIT, MAJ, MIN, WRN, RO

objid,fth

Alarm boost threshold

number see below

objid,bth

Alarm float threshold

number see below

Advertising