GE Industrial Solutions Pulsar Plus Controller User Manual

Page 187

Advertising
background image

Pulsar Plus Controller Family

Issue 7 December 2011

187

Table E-1 Alarms, Alarm Relays and LEDs Assignments – Pulsar Display

Severity - Relay and Display

Additional Relay

LED

Description

CRIT

PMJ

PMN

WRN

RO

R1

R2

R3

R4

R5

R6

R7

AC

DC

BD

Object

ID

No Dial-Out Response

WRN

POR1

Open String

MAJ

DC

OSA1

Password At Default

RO

PFD1

Processor Halt

RO

PHT1

Program Line Invalid

MAJ

PGI1

Queue Overflow

WRN

COF1

Real-Time Reserve Time Low

RO

RRTL1

Rectifier Current Limit

RO

CLM1

Rectifier Fail

MIN

R5

RFA1

Rectifier Fan Fail

MIN

R5

RFN1

Rectifier Redundancy Loss

MIN

R5

RLS1

Reserve Time Low

RO

RTL1

Ringer External Failure Major

MAJ

RPXJ1

Ringer External Failure Minor

MIN

RPXN1

Ringer Fail Major

MAJ

RPFJ1

Ringer Fail Minor

MIN

RF1

Ringer Fan Fail

MIN

RPFF1

Ringer ID Conflict

MAJ

RCDP1

Ringer Redundancy Loss

MIN

RPRL1

Self Test Failed

MIN

STF1

Sense Fuse

MIN

VSF1

Thermal Probe Failure

MIN

TPA1

Unconfigured Alarm Destination

WRN

NNC1

Un-powered Controller (Not
configurable)

x

x

x

x

x

x

x

Very High Battery Temperature

RO

BTVH1

Very Low Battery Temperature

RO

BTVL1

Very Low Voltage

CRIT

R2

VLA1

Voltage Duplicate ID

MAJ

MDP1

Voltage ID Not Configured

MAJ

MZD1

Voltage Imbalance Detect

MIN

SCD1

Voltage Monitoring Module Failure

MIN

VMF1

Table E-2 Alarms, Alarm Relays and LEDs Assignments – Phoenix Display

Severity - Relay and Display

Additional Relay

LED

Description

CRIT

PMJ

PMN

WRN

RO

R1

R2

R3

R4

R5

R6

R7

Object

ID

AC Fail

PMN

R1

ACF

ACF1

Alarm Cut-off Active

RO

ACO

AAC1

Alarm Test Aborted

RO

ATB1

Alarm Test Active

RO

ATA1

Auxiliary 1

MAJ

AUX1

Auxiliary 2

MAJ

AUX2

Auxiliary 3

MAJ

AUX3

Auxiliary 4

MAJ

AUX4

Auxiliary 5

MAJ

AUX5

Advertising