Pulsar Plus Controller Family

Issue 7 December 2011

20

Install and Configure Slot/Door-Mount Controllers

Step

Action

3

Configure alarm relays to “Open” or “Close” on alarm as required:

Jumpers 1-10 select the contact type provided at alarm connector J4 for each of the ten alarms.
Carefully move and verify each of respective configuration jumpers to achieve the desired
contact type: “Open On Alarm” or “Closed On Alarm” position. Use of an insulated tool is
suggested. Return the sliding cover on the slot-controller when configuration is complete. Note:
the same control board is utilized in all controller applications. However, the appearance of the
jumpers may seem different because of its orientation in the different packages. Use the
following along with labeling on the controller to assist in setting the jumpers.

Microprocessor Board - Integrated into all controllers

Each jumper corresponds to one alarm relay and each relay output can be configured
independently. The following table contains the alarms along with the factory default alarm
assignments to user relays R1-R7. Utilize the web or EasyView interface to reassign any of the
alarm outputs to specific alarm events or to change the severity of the alarms.

Slot Controllers - NE843A/CP843A/ED843D

Door Mount Controllers - NE843C/NE843E/NE843P