Table 44 Infinity NE System Troubleshooting

Alarm

Severity

Indicator

6

User Interface

Display

Rectifier

LED

Distribution

Module

Board LED

Possible Problem(s)

Possible Solution(s)

PMJ

RED

MIN, Rectifier

Fail

MAJ, Multiple

Rectifier Fail

MAJ, Battery on

Discharge

AC OK

ALARM

Normal

Multiple rectifier thermal
alarm: Excessive ambient
temperature
Multiple rectifier failure

1. Verify that there is no

obstruction of the vertical
airflow path.

2. Reset rectifies by removing

them, waiting approximately
30s and replacing them.

3. If problem persists, replace the

rectifiers.

4. If problem still persists, call your

local field representative.

PMJ

RED

MAJ, High
Voltage

AC OK

ALARM

Normal

High output voltage from
rectifier(s)
Rectifier(s) high voltage
shutdown
Internal rectifier(s) failure

1. Reset the rectifier(s) by

removing the rectifier(s),
waiting approximately 30s and
replacing the rectifier(s).

2. If problem persists, replace the

rectifier.

3. If problem still persists, call your

local field representative.

PMN

Amber

MIN, Clock

Battery Low

AC OK
DC OK

Normal

Internal Lithium Battery Is
Low

1. The battery is not designed to

be easily field replaced. The
controller unit needs to be
replaced.

2. Obtain all desired information

such as alarm history, statistics,
and any field configuration that
is different than the standard.

PMN

Amber

MIN, Minor

Communication
Fail

RED

Blinking

Single

rectifier

GREEN

Rectifier lost
communication with
controller.

1. If a rectifier has been removed

from an installed/operational
system, go to the
Control/Operations menu and
execute Uninstall Equipment.

2. Reset the rectifier by removing

the rectifier, waiting
approximately 30 seconds, and
replacing.

3. If problem persists, replace the

rectifier.

4. If problem still persists, call your

local field representative.

PMJ

RED

MAJ, Major

Communication
Fail

GREEN

RED (Blinking) LVD Board lost

communication with the
controller.

1. Replace Distribution Module

Board. (Note 2)

2. If problem persists, call your

local field representative.

Advertising