Pulsar Plus Controller Family

Issue 7 December 2011

124

System Inputs/Outputs Specifications

Item

Specification

SELV

All input and output connections comply with SELV requirements.

Connections - Ports

CAUTION
Intra-building ports of the equipment or subassembly

• are suitable for connection only to shielded intra-building or

unexposed wiring or cabling grounded at both ends.

• MUST NOT be metallically connected to interfaces which

connect to the OSP or its wiring.

These interfaces are designed for use as intra-building interfaces only
(Type 2 or Type 4 ports as described in GR-1089-CORE, Issue 5) and
require isolation from the exposed OSP cabling.

The addition of Primary Protectors is not sufficient protection.

All controller ports are intra-building except the phone port of the
BSM6 Modem.

Alarm and Control Inputs

(J3) 10-pin connector 2 control and 5 alarm inputs and returns;
(J1) 6-pin connector for 4 basic plant inputs

Alarm Contact Outputs

10 User configurable Form-C Outputs;
(J4) 20-pin connector for 10 individual alarm output contacts;
Wire size: 28-16 AWG stranded or solid

Alarm Contact Ratings

60 VDC, 0.5A

Plant Voltage Measurement

Accuracy

0 to 50°C

-40 to 85°C


Resolution


±0.05% of full scale + 1 count

48V Systems: ±40 mV; 24V Systems ±25 mV

±0.1% of full scale + 1 count)

48V Systems: ±70 mV; 24V Systems ±40 mV

0.01V

Plant Current Measurement

Accuracy

0 to 50°C

-40 to 85°C

Resolution


±0.5% of full scale
±1.25% of full scale
1A

Temperature Measurement
One-Wire Probe

Accuracy

-5 to +55°C

-40 to +85°C

Resolution



±1°C
±3°C
0.1°C