Pulsar Plus Controller Family

Issue 7 December 2011

149

CN1 = Battery Disconnect (LVBD1)
CN2 = Load 1 Disconnect (LVLD1)
CN3 = Load 2 Disconnect (LVLD2)
CN4 = Load 3 Disconnect (LVLD3)

Table 60 T1.317 Distribution Current Monitor Related Commands

obj,attr

Description

sta

cha

ope

type

Range of Values

dcmxx,ide

Identifier

number DCMC1 is the plant shunt

DCM01-DCM08

dcmxx,des

Description

number Contactor 1

dcmxx,stt

State

text

NONE
MISSING
PRESENT

dcmxx,typ

Shunt Type

text

NONE
LOAD
BATTERY

dcmxx,val

Reading

number ddd.d Amps

dcmxx,sha

Shunt amp rating

number 0-9999 Amps

The shunt type defaults are as follows:
DCMC1 = Battery
DCM01 = Battery
DCM02-DCM08 = Load

Table 61 T1.317 Distribution Contactor Interface Related Commands

obj,attr

Description

sta

cha

ope

type

Range of Values

dcnxx,ide

Identifier

number DCN01-DCN06

dcnxx,des

Description

number Contactor 1

dcnxx,stt

State

text

NONE
MISSING
OPEN
CLOSED

dcnxx,typ

Contactor interface type

text

NONE, CN1, CN2, CN3, or
CN4

The contactor interface type defaults are as follows:
DCN01 = CN1
DCN02 = CN2
DCN03 = CN3
DCN04-DCN08 = CN4

Table 62 T1.317 Slope Thermal Compensation Related Commands

obj,attr

Description

sta

cha ope

type

Range of Values

sc1,ide

Identifier

Text

SC1

sc1,des

Description

Text

Slope Thermal Comp

sc1,stt

State

number 0=disable 1=enable

sc1,rve

Raise Voltage Enable

number 0=disable 1=enable

sc1,ltt

Lower Temperature Threshold

number -5-20°C or 23-68°F

sc1,ntt

Nominal Temperature Threshold

number 15-30°C or 59-86°F

sc1,utt

Upper Temperature Threshold

number 30-55°C or 86-131°F

sc1,spt

Step Temperature

number 45-85°C or 113-185°F

sc1,lsp

Low temperature slope

number 1-10mV/°C per cell

sc1,usp

Upper temperature slope

number 1-10mV/°C per cell