Pulsar Plus Controller Family

Issue 7 December 2011

161

30-JAN-2003,05:00:00,120.1
31-JAN-2003,14:00:00,122.8
DLI=
29-JAN-2002,12:00;00,120.9
30-JAN-2003,08:00:00,118.7
31-JAN-2003,01:00:00,119.2
DHH=
29-JAN-2002,02:00;00,122.1
30-JAN-2003,05:00:00,119.7
31-JAN-2003,14:00:00,121.6
MAV=
31-JAN-2003,23:00:00,121.3
.
*

The “DHI=” indicates daily highest hourly instantaneous reading. The “DLI=” indicates daily
highest hourly instantaneous reading. The “DHH=” indicates daily highest hourly average
reading. The “MAV=” indicates monthly average of daily highest hourly average reading. The
“.” line is the end-of-command identifier. The “* ” in the example above is the user command
line prompt.

sum

Report Battery Discharge Statistics (Profile)

Syntax:

sum dc1,bod

Description
This command reports the last battery discharge profile report. The report includes cleared
date and time, start date and time, end date and time, duration in seconds, and up to 50
sample points. Each sample is time stamped in seconds. We compress the samples to derive a
minimum set of data required to reconstruct the curve while retaining important coup de
fouet minimum and maximum voltages and lowest voltage at end of discharge. The following
is an example of a command response:

* sum dc1,bod
:DC1 BOD
CLR=29-JUN-04,10:27:11
BEG=30-JUN-04,10:38:36
END=30-JUN-04,10:42:53
DUR=256
VAL=
0,51.08
8,50.18
18,49.24
20,48.87
248,48.36
252,49.76
254,50.84
256,51.13
.
*

The “.” line is the end-of-command identifier. The “* ” in the example above is the user
command line prompt.