Table 70 t1.317 local rs-232 port related commands, Table 71 t1.317 alarm test related commands – GE Industrial Solutions Pulsar Plus Controller User Manual

Page 152

Advertising
background image

Pulsar Plus Controller Family

Issue 7 December 2011

152

ADMINISTRATOR, TL1,
LOGOUT

mp1,bdr

Modem baud rate

text

2400,4800,9600

mp1,dbt

Data Bits

Number 7, 8

mp1,pry

Parity

text

O, E, N

mp1,sbt

Stop Bits

Number 1, 2

mp1,tmo

Time-Out

Number 0(disabled) – 45 minutes

mp1,hsh

Handshaking

text

NO, SW

mp1,nrg

Number of Rings Before Answer

number 2-15

mp1,wre

Write Enable

Number 0=disable 1=enable (HW,SW)

mp1,ins

Modem Initialization String

text

Up to 40 characters “”
assigns the default string

Table 70 T1.317 Local RS-232 Port Related Commands

obj,attr

Description

sta

cha

ope

type

Range of Values

lp1,des

Description

text

Local Port 1

lp1,stt

State

text

USER, SUPER-USER,
ADMINISTRATOR, TL1,
LOGOUT

lp1,bdr

Baud Rate

text

AUTO, 300, 1200, 2400,
4800, 9600, 19200

lp1,dbt

Data Bits

Number 7, 8

lp1,pry

Parity

text

O, E, N

lp1,sbt

Stop Bits

Number 1, 2

lp1,tmo

Time-Out

Number 0(disabled) – 45 minutes

lp1,hsh

Handshaking

text

NO, HW, SW

lp1,app

Application

Text

TERMINAL, EVENT LOG
(HW,SW)

lp1,wre

Write Enable

Number 0=disable 1=enable (HW,SW)

Table 71 T1.317 Alarm Test Related Commands

obj,attr

Description

sta

cha

ope

type

Range of Values

at1,des

Description

Text

Alarm Test 1

at1,stt

Alarm Test State

Number 0=inactive 1=active

at1,stg

Alarm Test Stage

text

PCR,PMJ,PMN,R1,R2,R3,R4,R
5,R6,R7

at1,lte

Alarm Test Enable

Number 0=disable 1=enable (HW,SW)

at1,dur

Duration

Number 5-300 seconds

at1,pcr

Test Power Critical

Number 0=no 1=yes

at1,pmj

Test Power Major

Number 0=no 1=yes

at1,pmn

Test Power Minor

Number 0=no 1=yes

at1,r1

Test Relay 1

Number 0=no 1=yes

at1,r2

Test Relay 2

Number 0=no 1=yes

at1,r3

Test Relay 3

Number 0=no 1=yes

at1,r4

Test Relay 4

Number 0=no 1=yes

at1,r5

Test Relay 5

Number 0=no 1=yes

at1,r6

Test Relay 6

Number 0=no 1=yes

at1,r7

Test Relay 7

Number 0=no 1=yes

at1,ets

Email Test

number 1=do test (sets and clears

ATA1)

at1,ems

Email Results

text

at1,bzi

Audio Test Duration

Number 5-300 seconds

at1,bzt

Audio Test State

Number “”=Stop Test, Local=local

Advertising