Pulsar Plus Controller Family

Issue 7 December 2011

26

Install and Configure Pulsar Plus NE843G Controller

Step

Action

7

Configure alarm relays to “Open” or “Close” on alarm as required:

Jumpers 1-10 select the contact type to provide at alarm connector J4 of each respective Form-
C output for each alarm. Carefully move each of respective configuration jumpers to the desired
contact type: “Open On Alarm” or “Closed On Alarm” position as required per site instructions.
Use of an insulated tool is suggested. Return the cover on the controller if finished configuring
alarm relays and 1-Wire reference adjustment is not required. Note: the same control board is
utilized in all controller applications. However, the appearance of the jumpers may seem
different because of its orientation in the different packages. Use the following along with
labeling on the controller to assist in setting the jumpers.

Each jumper corresponds to one output alarm relay contact that can be independently
configured. The alarm table shown in Step 3 previously is also applicable for this controller but
repeated below for convenience. Utilize the web or EasyView interface to change any of the
alarm user relay alarm assignments.