Pulsar Plus Controller Family

Issue 7 December 2011

99

Step

Action for Voltage Imbalance Mid-String Monitoring

probe to the ES771 module.

5

Connect another ES771A to the controller by connecting an additional 848652947 wire set from
the first module to the RJ45 receptacle on the second module.

Verify the number of modules (2) registered with the controller with command:
MenuStatusBatteriesNum Mid-String V

6

Repeat Step 5 until all modules are installed. Verify that all probes are also automatically
detected by the controller at the front panel at: MenuStatusBatteriesNum Temp Probes

7

If the LEDs on the module(s) are not illuminated green on or are red or if the number of
registered modules does not agree with the number used: Check integrity of all cable
connections

8

Issue the Clear Events command: MenuControl/OperationsClear Events. If the LEDs are still
not lit green or if the number of registered modules still does not agree, call your local field
representative.


The system is now set to monitor both voltage and temperatures to support the batter string voltage
imbalance and slope thermal compensation features. Figure 16 depicts a reserve system where every
battery in the string being monitored for temperature. Again, the highest temperature measured will be
used for battery thermal management. Only one temperature probe is required for thermal compensation
features.

Figure 16: Same System Monitored For Imbalance With VT Probe On Every Battery