cha

Change Value

Syntax:

cha obj,attr=value
where: obj,attr is an object-attribute pair. For example, ps1,sid.

Description
This command is used to change system configuration parameters. Examples are listed below
to illustrate how this command works.

cha ps1,sid="My Plant"Change the site id to My Plant
cha p1,phn="123456789"Change the primary phone number to 123456789

You must be logged in as a super-user to use this command.

cle

Clear All Latched Events

Syntax:

cle

Description
This command is used to clear latched events. These events include communication failures,
missing rectifiers, missing thermal probes, missing voltage monitoring module, distribution
fuses, and loss of redundancy alarm.

You must be logged in as a super-user to use this command.
his

Report Alarm History

Syntax:

his

Description

Syntaxhis

where: obj,attr is an object-attribute pair as defined in the following:
sum dc1,adc- report plant load current statistics
sum br1,hbt- report highest battery temperature statistics

his

Report Boost History

Syntax:

his bs1,stt

Description
This command reports the boost history in the following format:
sum bs1,stt
30-MAY-03,15:11:12,RESUMED,COMPLETED,78
30-MAY-03,12:03:34,AUTO,DISCHARGE,14

**

This report gives the start date, start time, start reason, stop reason, and boost duration in
minutes. The start reasons are:
MANUALBoost initiated by user
AUTOBoost started automatically after a battery discharge
RESUMEDBoost resumed after being suspended by a discharge

The stop reasons are:
COMPLETEDBoost completed normally
TIMEOUTBoost timed out before completing
DISCHARGEBoost suspended because of a battery discharge
CANCELEDBoost canceled by user
ALARMBoost cancelled by an alarm condition