Pulsar Plus Controller Family

Issue 7 December 2011

56

Status LEDs - Pulsar

Pulsar controller displays provides three LED indicators to provide more specific indications of the system
status. These LEDs provide specific indication concerning the AC and DC system status and Battery on
Discharge state. These LEDs have factory assigned defaults as indicated in the table below. However, the
assignments to alarms can be customized in the field using the remote interfaces.

Table 8 Status LEDs - Pulsar

LED

Status

Condition

AC input to all rectifiers is in range.

AC

AC input to one rectifier is missing or out of range.

AC input to two or more rectifiers is missing or out of range.

DC output to all loads is normal.

DC

One or more of the following alarms are present: Fuse Minor 48, Fuse Minor 24

One or more of the following alarms are present: Open String, LVBD Open, Fuse
Major 48, Fuse Major 24

System above configured Battery on Discharge (BD) threshold.

BD

State not presently assigned.

System equal to or below configured Battery on Discharge (BD) threshold.