Table d-2 24v battery related items defaults – GE Industrial Solutions Pulsar Plus Controller User Manual

Page 183

Advertising
background image

Pulsar Plus Controller Family

Issue 7 December 2011

183

Table D-2 24V Battery Related Items Defaults

Category

Description

Range

Valve-Reg

Flooded

Li_ELiTE

NiCd

Li-LMP

obj,attr

Voltage Settings

Float Rectifier High Voltage Shutdown

25 to 30V

29.25

29.25

29.25

29.25

29.25

GM1,FSD

Float High Voltage Major Alarm

25.74 to 31.75V

28.24

28.24

28.24

28.24

28.24

HVA1,FTH

Float High Voltage Minor Alarm

24.75 to 29.75V

27.74

27.74

27.74

27.74

27.74

HFV1,FTH

Float Voltage

21 to 28V

27.24

26.04

27.24

27.20

27.24

GM1,FSP

Float Battery on Discharge Alarm

23 to 28V

25.54

25.00

26.50

25.54

25.54

BDA1,FTH

Very Low Voltage Alarm

20 to 25.5V

23.00

23.00

23.00

23.00

23.00

VLA1,THR

Rectifier On Threshold

20 to 25V

22.00

22.00

22.00

22.00

22.00

DC1,ROT

Battery Disconnect

LV Battery Disconnect

1=Enabled

0=Disabled

1

1

0

1

0

CN1,ENA

LV Battery Disconnect Voltage

19.5 to 25V

21.00

21.00

21.00

21.00

21.00

CN1,DTH

LV Battery Reconnect Voltage

19.5 to 25V

22.20

22.20

22.20

22.20

22.20

CN1,RTH

Batteries

Cells Per String

0-75

12

12

12

12

12

DC1,CPS

String End Of Discharge Voltage

19.25 to 25.35

21.00

21.00

21.00

21.00

21.00

BR1,CEV

Recharge Current Limit Feature

1=Enabled

0=Disabled

0

0

0

0

0

BR1,CLE

Recharge Current Limit Value

5 to 1000A

50

50

25

25

25

BR1,CLT

Boost Maximum Duration

1 to 80 Hours

1

1

1

1

1

BS1,TMD

Voltage Imbalance Detect

1.5V to 3.0V

1.7

1.7

1.7

2.0

1.7

BR1,SCV

High Temperature Disconnect

30 to 90

o

C

75

75

75

75

75

BR1,TTH

High Battery Temperature

30 to 85

o

C

55

55

55

55

85

BTHA1,THR

Battery Slope

Compensation

Slope Thermal Compensation (STC)

1=Enabled

0=Disabled

1

0

0

0

0

SC1,STT

High Temperature Voltage Step Down

45 to 85

o

C

75

75

75

75

75

SC1,SPT

High Temperature Compensation Stop

30 to 55

o

C

55

55

55

55

55

SC1,UTT

High Temperature Decrease Rate

1-10mV/

o

C per

cell

3

3

3

3

3

SC1,USP

Nominal Temperature (No Temp
Comp)

15 to 30

o

C

25

25

25

25

25

SC1,NTT

Low Temperature Compensation
Feature

1=Enabled

0=Disabled

0

0

0

0

0

SC1,RVE

Low Temperature Compensation Stop

-5 to 20

o

C

0

0

0

0

0

SC1,LTT

Low Temperature Decrease Rate

1-10mV/

o

C per

cell

3

3

3

3

3

SC1,LSP

Battery Discharge Test

Timed Test Alarm Voltage Threshold

21 to 27V

22.00

22.00

23.00

22.00

22.00

BR1,TEV

Rectifier Voltage During Battery Test

21 to 26V

21.00

21.00

21.00

21.00

21.00

BR1,BTV

Battery Boost

Boost Rectifier High Voltage Shutdown

26 to 30V

29.25

29.25

29.25

29.25

29.25

GM1,BSD

Boost High Voltage Major Alarm

25.75 to 31.75V

28.24

29.00

28.24

28.24

28.24

HVA1,BTH

Boost High Voltage Minor Alarm

25.75 to 31.75V

27.74

28.00

27.74

27.74

27.74

HFV1,BTH

Boost Voltage

22 to 30V

27.24

26.04

27.24

27.20

27.24

GM1,BSP

Boost Battery on Discharge Alarm

23 to 28V

25.54

25.00

26.50

25.54

25.54

BDA1,BTH

Advertising