GE Industrial Solutions Pulsar Plus Controller User Manual

Page 75

Advertising
background image

Pulsar Plus Controller Family

Issue 7 December 2011

75

Table 20 Control/Operations

Uninstall Equipment Clears alarms related to the removal of a system component such as a rectifier,

converter, thermal probe, or voltage monitoring module. Running this
command allows the system controller to retake inventory of using equipment.

Clear History

This area of the menus system can be used to clear the various items that the
controller maintains history records. Once cleared the controller begins to keep
history of new events.

Alarm History

Clears only alarm event history.

BD History

Clear only BD network access history.

Rectifier History

Clears only rectifier event history.

Converter History

Clears only converter event history.

Boost History

Clears only Boost event history.

Local Port History

Clears only local port access event history.

Modem History

Clears only Modem port access event history.

Network History

Clears only network access history.

All History

Single command to clear all history.

Clear Statistics

This area of the menus system can be used to clear the various items that the
controller maintains statistical records. Once cleared the controller begins to
keep new statistical data.

Clear Basic Clears individually or as a group the Basic statistical data kept on

Plant Load, the highest battery temperature, and ambient.


Clear Trend Clears the trend data kept on the plant load.

Clear BD

Clears the Battery on Discharge (BD) statistics kept on the plant
load and voltage during discharge.

Alarm Test

Provides ability to initiate an alarm test on a specific user selected output relay
or all output relays. Alarm relays are asserted at the configured alarm interval.

Start Battery Test

Initiates the manual battery test feature. A stop battery test operation is
displayed to interrupt the testing and return the unit to normal operation. The
manual battery test utilizes the configured test duration and a system bus
voltage threshold to represent the end of reserve.

Disconnects

Provides individual manual control of up to four Low Voltage Disconnects
(LVBD, LVLD1-3) for maintenance purposes.

Enter Boost

Initiates the manual battery Boost feature. A stop battery Boost operation is
displayed to interrupt the Boost operation mode and return the unit to normal
operation.

Load Config Defaults This operation allows a user to bring back all factory defaults with a single

operation. Factory defaults are also custom configuration defaults that are
available. Custom configurations may support multiple factory defaults. Use
caution when applying this command. Previous configuration changes will be
overwritten.

Reset Passwords

Resets user, super-user and administrator passwords back to standard defaults.