Table E-1 Alarms, Alarm Relays and LEDs Assignments – Pulsar Display

Severity - Relay and Display

Additional Relay

LED

Description

CRIT

PMJ

PMN

WRN

RO

R1

R2

R3

R4

R5

R6

R7

AC

DC

BD

Object

ID

Controller Ambient Temperature High

MIN

AMTH1

Controller Ambient Temperature Low

MIN

AMTL1

Controller Fail (Not user mappable)

x

x

x

Converter Distribution Fuse

MAJ

DC

CDFA1

Converter Fail

MIN

R5

CFA1

Converter Fan Major

MAJ

R5

CFJ1

Converter Fan Minor

MIN

R5

CFN1

Converter Low Voltage

CRIT

R2

CVLA1

Converter High Voltage Major

MAJ

R7

CHVA1

Converter High Voltage Minor

MIN

R7

CHFV1

Converter ID Conflict

MAJ

CDID1

Converter Redundancy Loss

MIN

R5

CRL1

Defective Temp Probe

MIN

TPA1

Emergency Power Off (EPO)

MAJ

EPO1

Energy Management Disabled

WRN

EMD1

Excessive Login Attempts

WRN

EXL1

External Password Reset

WRN

EPR1

Fuse Major 24

MAJ

R3

DC

FAJ1

Fuse Major 48

MAJ

R3

DC

FAJ2

Fuse Minor 24

MIN

R3

DC

FAN1

Fuse Minor 48

MIN

R3

DC

FAN2

Generator Requires Maintenance

MAJ

GNM1

Generator Running

MIN

GNR1

High Voltage Major

MAJ

R7

HVA1

High Voltage Minor

MIN

R7

HFV1

History Cleared

RO

HCL1

ID Conflict

MAJ

DID1

ID Not Configured

MAJ

ZID1

Imminent LVBD Shutdown

MAJ

DC

ISD1

Incompatible Converter

MIN

ICC1

Incompatible Rectifier

MIN

ICR1

Low Battery Temperature

RO

BTLA1

LV Disconnect Contactor 1 Fail

MAJ

CNF1

LV Disconnect Contactor 1 Open

MAJ

DC

CNO1

LV Disconnect Contactor 2 Fail

MAJ

CNF2

LV Disconnect Contactor 2 Open

MAJ

CNO2

LV Disconnect Contactor 3 Fail

MAJ

CNF3

LV Disconnect Contactor 3 Open

MAJ

CNO3

LV Disconnect Contactor 4 Fail

MAJ

CNF4

LV Disconnect Contactor 4 Open

MAJ

CNO4

Manual Off

MIN

R5

MAN1

Multiple AC Fail

MAJ

R6

AC

MACF1

Multiple Converter Fail

MAJ

R6

CMFA1

Multiple Manual Off

MAJ

R6

MMAN1

Multiple Rectifier Fail

MAJ

R6

MFA1

No Call-Out Response

WRN

COR1