Rectifiers, Table 25 rectifiers configuration – GE Industrial Solutions Pulsar Plus Controller User Manual

Page 81

Advertising
background image

Pulsar Plus Controller Family

Issue 7 December 2011

81

Table 24 Shunt Type Configuration

Shunt

Type

System Configuration

Controller Operation

Shunt input may or may not be
connected to a shunt located in the
system. System has Shunt Monitors
configured in the system and all system
loads are monitored.

And

The new “All Load Monitored” feature
has been “Enabled”.

1. Cards configured to monitor “Battery”

shunts are assumed to monitor all battery
current to and from the system batteries
and are summed to the total battery
current ( I

battery

). In addition, all individual

battery monitor values are displayed

2. Cards configured as monitoring a “Load”

shunt are summed to calculate the total
I

Load

and also have their individual values

displayed.

Thus, the controller reports the following:

I

battery

= Σ I

battery shunt monitors

I

Load

= Σ I

Load shunt monitors

Note: If there are no Battery Shunt Monitors
configured but the total load monitored is
enabled, then the total battery current is
calculated as follows:

I

battery

= Unavailable

I

Load

= Σ I

Load shunt monitors

Recharge current feature is unavailable.

Rectifiers

Table 25 Rectifiers Configuration

Redundancy

An alarm is automatically generated when the rectifier capacity On-line in the
system falls below N+X based on the present system load. X is the desired
number of rectifiers to check for redundancy.

The factory default for this feature is Enabled and X=1.

Rectifier On
Threshold

The system DC bus threshold that rectifiers placed into Standby will
automatically be turned on.

This value can be set between -40.00V and -51.00V and +20.00V to +25.00V
with factory defaults set to -44.0V and +22.00V for 48V and 24V rectifiers,
respectively.

Remote Off

Provides the ability to disable or enable the capability of placing a rectifier into
Standby operation through remote means such as the network, modem, or
local terminal.

The factory default for this feature is Disabled.

Sequencing

When enabled, provides the ability to hold off a user configured group of
rectifiers when appropriate contact closure is received, The feature is also
called Group Standby.

The factory default for this feature is Disabled.

Current Limit

Adjustable from 30-100%. At 100% the rectifier will output its nameplate rating