Table 46 T1.317 Power System Related Commands

obj,attr

description

sta

cha ope

type

Range of Values

ps1,sys

System Description

text

Up to 55 characters

ps1,swv

Software version

text

d.d

ps1,verw

Web pages version

text

d.d

ps1,verb

Boot block version

text

d.d

ps1,verd

Display version

text

d.d

ps1,dflt

Defaults version

text

d.d

ps1,brc

Board code

text

“”

ps1,sn

Serial number

text

YYLLdddddddd

ps1,dow

Day of week

Text

Sunday…Saturday

ps1,dat

Date

date

format matching ps1,dtf

ps1,dtf

Date format

text

mm-dd-yyyy, dd-mm-yyyy, yyyy-
mm-dd

ps1,tim

Time

time

hh:mm

ps1,tmf

Time format

number 12, 24

ps1,dls

Daylight savings enable

number 0=disabled 1=enabled

ps1,lng

Language

text

ENGLISH, OTHER
OPE changes the descriptions

ps1,tun

Temperature units

text

C, F

Ps1,cem

Critical equals major

number 0=disable, 1=enable

ps1,fpc

Front panel configuration

number 0=disable, 1=enable

ps1,rrf

Remote rectifier off

number 0=disable, 1=enable

ps1,poe

Power off enable

number 0=disable, 1=enable

ps1,usl

Uninstall missing equipment

number 1

ps1,usr

Username enable

number 0=disable, 1=enable

ps1,dct

Display contrast

number 0 – 100 %

ps1,ptt

Communication port type

text

“LOCAL”,”MODEM”

ps1,amt

System ambient temperature

number dd °C

ps1,fst

Factory defaults

text

See ps1,fstl

ps1,fstl

Factory defaults list

text

Comma deliminated list of
defaults

ps1,rap

Reset Passwords

number 1 = reset passwords (OPE only

valid from local display) will
restore passwords.gal

ps1,fpe *

Front Panel Pin enable

number 0=disable, 1=enable

ps1,fpt *

Front Panel Pin Time-out

Number 1-120 minutes

Ps1,fpp *

Front Panel Pin

Number 4 digit Pin (only viewable as

admin)

ps1,rss

Restart all

number 1=restart rectifiers and ringers

ps1,ltt

Lamp test

number 1 = do lamptest

ps1,ast

System alarm state

Text

“NORM, "RO", "WRN", "MIN",
"MAJ", "CRIT"

ps1,slv

Port security level

text

ps1,dss

Daylight saving start

d:d:d:d

mon:wk:dow:min
mon:-1:dom:min

ps1,dse

Daylight saving end

d:d:d:d

mon:wk:dow:min
mon:-1:dom:min

Ps1,uet

Uninstall Timeout

Number 0-60

* Must have administrator privileges to change.