Pulsar Plus Controller Family

Issue 7 December 2011

185

Appendix E: Alarms and Relays

Alarm Relays

The control unit is provided with ten alarm relays; seven to provide the actual alarm condition, and three to
provide the severity associated with the alarm. The severity relays transmit Power Critical (PCR), Power
Major (PMJ), or Power Minor (PMN). Each alarm is factory assigned a severity based on industry practices.
However, they may be reassigned to PCR, MAJ, MIN, or RO (Record Only). An alarm condition with the RO
severity results in the system controller transmitting the alarm without the severity but is stored in the
history log. PCR, PMJ nor PMN are transmitted with the alarm.

The seven selectable alarm relays are called User Alarm Relay 1 (R1) through User Alarm Relay 7 (R7). Relays
are user definable in that the user may assign any combination of alarms from a given set of alarms. The
following table shows which alarms may be assigned along with their factory default settings.

Alarms

Table E-1 shows a list of all alarms along with their descriptions, default settings, ranges and/or severity, and
affected alarm relays and LEDs.

Table E-1 Alarms, Alarm Relays and LEDs Assignments – Pulsar Display

Severity - Relay and Display

Additional Relay

LED

Description

CRIT

PMJ

PMN

WRN

RO

R1

R2

R3

R4

R5

R6

R7

AC

DC

BD

Object

ID

AC Fail

MIN

R4

AC

ACF1

Alarm Cut-off Active

RO

AAC1

Alarm Test Aborted

RO

ATB1

Alarm Test Active

RO

ATA1

Auxiliary 1

MAJ

AUX1

Auxiliary 2

MAJ

AUX2

Auxiliary 3

MAJ

AUX3

Auxiliary 4

MAJ

AUX4

Auxiliary 5

MAJ

AUX5

Auxiliary 6

MAJ

AUX6

Auxiliary 7

MAJ

AUX7

Auxiliary 8

MAJ

AUX8

Auxiliary 9

MAJ

AUX9

Auxiliary 10

MAJ

AUX10

Auxiliary 11

MAJ

AUX11

Auxiliary 12

MAJ

AUX12

Auxiliary Major Alarm

MAJ

AMJ1

Battery Test Active

RO

BD

BTA1

Battery on Discharge (Float and Boost)

MAJ

R1

BD

BDA1

Battery Thermal alarm

MIN

BTHA1

Check Battery

MIN

BFA1

Clock Battery Low

MIN

BBL1

Clock Changed

RO

CLC1

Communication Loss Major

MAJ

MCM1

Communication Loss Minor

MIN

CMA1

Configuration Changed

RO

CCH1