Batteries, Table 26 batteries configuration – GE Industrial Solutions Pulsar Plus Controller User Manual

Page 82

Advertising
background image

Pulsar Plus Controller Family

Issue 7 December 2011

82

Table 25 Rectifiers Configuration

and truly act as constant power rectifiers. Settings below 100% will be current
limited to that percentage of the rectifier’s name plate current rating.

Batteries

Table 26 Batteries Configuration


Battery Type

The type of batteries used in the system can be selected from the following
battery types loaded in the Standard controller:

• 12A100FT

• 12A150FT

• 12IR150/150LP

• 3A125-33L

• 3A95-21L

• 3A95-27L

• 3A95-33L

• 6A95-13L

• 6A95-15L

• IR30EC

• IR40EC

• L54V63FTX

• NCX-125

• NCX-80

• NSB110FT

• NSB170FT

• NSB60FT

• SE48S63

• SE48S80

• TEL12-105F

• Generic VRLA (Valve Regulated

Lead Acid)

• Generic FLOODED (flooded lead

acid)

• Generic NiCd (Nickel Cadmium) • Generic Li-ELiTE (Lithium ELiTE)
• Generic Li-LMP (Lithium Metal

Polymer)


Once selected the user has the opportunity to automatically accept the
standard defaults for all battery Type related features. Parameters such as float
voltage, float alarms, thermal compensation parameters, etc. are automatically
adjusted if defaults are accepted.

The system factory default is Valve-Reg.


String Capacity


Capacity of an individual battery string in the system which is used to derive the
total installed system battery capacity. This value has to be entered for Generic
battery types but is automatically configured for specific battery models. The
value configured should be the rating to 1.75V at an 8-hr discharge rate.

The available range is 0-9999 AH. The system factory default is 0 AH
corresponding to the Generic Valve-Reg.


Battery Strings


The total number of battery string installed in the system entered by the user
for inventory purposes and initial reserve time calculations. This value is
automatically configured when using smart lithium batteries. Available range is
0-16. The Infinity NE system factory default is four strings of CSL-12100
batteries.


Cells Per String


The number of basic battery cells that make up a battery string.

The available range is 1-75 cells with a factory default of 24 and 12 cells for -48V
and +24V systems, respectively.

Advertising