Troubleshooting, Table 44 infinity ne system troubleshooting – GE Industrial Solutions Pulsar Plus Controller User Manual

Page 119

Advertising
background image

Pulsar Plus Controller Family

Issue 7 December 2011

119

Troubleshooting

Table 44 Infinity NE System Troubleshooting

Alarm

Severity

Indicator

6

User Interface

Display

Rectifier

LED

Distribution

Module

Board LED

Possible Problem(s)

Possible Solution(s)

PMN

AMBER

MIN, AC Fail

None

GREEN

Single Rectifier not
receiving ac power.

AC input circuit breaker
has opened.

AC input voltage is out
of range

.

1. Verify ac power to rectifier is

available.

2. Verify rectifier input circuit

breaker is closed.

3. If problem not corrected,

replace rectifier.

PMJ

RED

MIN, AC Fail
MAJ, Multiple

AC Fail

MAJ, Battery on

Discharge

None

GREEN

Multiple rectifiers not
receiving ac power,
batteries are powering
load.

AC input circuit breakers
have opened.

AC input voltage is out
of range.

Internal rectifier fault.

4. Verify ac power to rectifiers is

available.

5. Verify rectifier input circuit

breakers are closed.

6. If problem not corrected,

replace rectifier.

PMJ or

PMN

AMBER or

RED

MIN, AC Fail

MAJ, Multiple

AC Fail

None

GREEN

A rectifier, multiple
rectifiers, or the entire
system has lost AC and
one or more rectifiers
have been removed from
the system while under
this condition.

1. Verify that ac power to all

rectifiers is available.

2. Verify that rectifiers all

report good AC

3. Issue the uninstall equipment

under the operations menu
for any rectifier that may
have been removed during
the AC fail.

PMJ

RED

MAJ, Battery on

Discharge

AC OK
DC OK

GREEN

Rectifier output voltage
has fallen below the
battery on discharge
threshold set by the user.

1. If commercial ac power is

present but the system voltage
remains low, call your local
field representative.

2. Investigate other alarms that

may be present such as
rectifier related problems.

PMN

AMBER

MIN, Rectifier

Fail (Note 1)

AC OK

ALARM

(Note 1)

GREEN

Rectifier output has
dropped below 36V,
rectifier has entered
hiccup mode.

Replace rectifier.

PMJ

RED

MAJ, Rectifier

Fail

AC OK

ALARM

(Note 1)

GREEN

All rectifier outputs have
dropped below 36V, all
rectifiers have entered
hiccup mode.
Defective controller.

Remove controller; if output
voltage does not go to set-point
previously set by user, call your
local field representative.

6

Pulsar Displays – Alarm Severity indicated by back-light color of the display: Red = Critical or Major, Amber = Minor,

Green = Normal.
Phoenix Displays – Alarm Severity indicated by separate LEDs: PCR (Red) = Critical, PMJ (Red) = Major, PMN (Amber)
= Minor, SYSOK (Green) = Normal