Table 2 controller standard defaults door mounted – GE Industrial Solutions Pulsar Plus Controller User Manual

Page 21

Advertising
background image

Pulsar Plus Controller Family

Issue 7 December 2011

21

Install and Configure Slot/Door-Mount Controllers

Step

Action

Jumper

Number

Signal
Name

Table 2 Controller Standard Defaults Door Mounted

Pulsar Plus Display

Phoenix Display

1

PCR

Power Critical Alarm severity indicator

2

PMJ

Power Major Alarm severity indicator

3

PMN

Power Minor Alarm severity indicator

4

R1

Battery on Discharge alarm

(BD)

AC/Multiple AC Fail

(ACF, MACF)

5

R2

Very Low Voltage alarm

(VLV)

Battery on Discharge, Battery Test

Active

(BD, BTA)

6

R3

Fuse Alarm

(FAJ1/2/FAN1/2)

Distribution Fuse/CB Alarm, Open

String

(FAJ1/2, FAN1/2, CDFA, AMJ, OSA)

7

R4

AC Fail alarm

(ACF)

High Voltage

(HVA, HFV)

8

R5

Rectifier/Converter Fail

alarm

(RFA/ CFA)

Rectifier Fail, Incompatible

Rectifier

(RFA, RFN, ICR)

9

R6

Multiple Fail alarm

Rectifier/Converter/AC

(MACF/MRFA/

MCFA/MMAN)

Multiple Rectifier Fail

(MRFA/MFA)

10

R7

High Voltage alarm -

Rectifier and Converter

(HVA/HFV/CHVA/CHFV

Converter Fail/Multiple Converter

Fail, Converter Redundancy Loss,

Converter Low Voltage, Converter

High Voltage, Converter ID

Conflict

(CFA, MCFA, CFN, CRL, CVLA,

CHVA, CHFV, CDID)

If your system using the optional ES771 Mid-String Voltage Modules continue with Step 4.
Otherwise go to step 5.