Table 72 t1.317 alarm cut-off related commands, Table 74 t1.317 derived channels related commands – GE Industrial Solutions Pulsar Plus Controller User Manual

Page 153

Advertising
background image

Pulsar Plus Controller Family

Issue 7 December 2011

153

Table 71 T1.317 Alarm Test Related Commands

obj,attr

Description

sta

cha

ope

type

Range of Values

buzzer

at1,irt

Individual Relay Test State

Number “”=Stop Test,

PCR,PMJ,PMN,R1,R2,R3,R4,R
5,R6,R7

Table 72 T1.317 Alarm Cut-off Related Commands

obj,attr

Description

sta

cha

ope

type

Range of Values

aco1,des

Description

Text

Alarm Cut-off 1

aco1,stt

Alarm Cut-off State

Number 0=inactive 1=active

aco1,cst

Critical Alarm Cut-off State

Number 0=inactive 1=active

aco1,cae

Critical Alarm Cut-off Enable

Number 0=disable 1=enable

aco1,cto

Critical Alarm Cut-off Time-Out

Number 1 to 8 hours

aco1,jst

Major Alarm Cut-off State

Number 0=inactive 1=active

aco1,jae

Major Alarm Cut-off Enable

Number 0=disable 1=enable

aco1,jto

Major Alarm Cut-off Time-Out

Number 1 to 8 hours

aco1,nst

Minor Alarm Cut-off State

Number 0=inactive 1=active

aco1,nae

Minor Alarm Cut-off Enable

Number 0=disable 1=enable

aco1,nto

Minor Alarm Cut-off Time-Out

Number 1 to 72 hours

aco1,lbe

Local Buzzer Enable

Number 0=disable 1=enable

Table 73 T1.317 User Defined Events Related Commands

obj,attr

Description

sta

cha

ope

type

Range of Values

unnnn,des Description

Text

30 char

unnnn,fds

Front Panel Description

text

see below

unnnn,ast

Alarm State

Number 0=inactive 1=active

unnnn,sev Severity

Text

CRIT, MAJ, MIN, WRN, RO

unnnn,prg Program Line

Text

60 char

unnnn,dur Minimum Duration

Number > 0 seconds

unnnn,lat

Latched

Number 0=no 1=yes

unnnn,led

LED

text

BD,AC,DC,””

unnnn,acc Contact Closure

text

R1,R2,R3,R4,R5,R6,R7,””

unnnn,dly

Notify Delay

Number 0-540 seconds

unnnn,no
o

Notify On Occur

Number 0=no 1=yes

unnnn,nor Notify On Retire

Number 0=no 1=yes

unnnn,nag NAG On Occur

Number 0=no 1=yes

unnnn,dst

Notify Destination

text

“”, P1, P2, P3, P4, E1, E2, E3,
E4, S1, S2, S3, S4

where nnnn = 1 thru 128

Table 74 T1.317 Derived Channels Related Commands

obj,attr

Description

sta

cha

ope

type

Range of Values

DRnn,des

Description

Text

30 char (Derived Chan nn)

DRnn,val

Value

Number Number units

DRnn,prg

Program line

Text

60 char

DRnn,uni

Unit

Text

5 chars

Where nn is from 01 thru 8