172

Table D-1 Standard Configuration Item Defaults

Factory Default

Factory 24V

Rectifier

Default

Factory 48V

Rectifier

Default

Category

Description

Range

Factory

Factory 24V

Factory 48V

obj,attr

Controller

Site ID

≤ 20 characters

""

PS1,SID

Site Description

≤ 55 characters

""

PS1,SDE

Controller Description

Plant Description

"NE843A"

PS1,DES

System Description

≤ 55 characters

"Infinity NE"

PS1,SYS

Plant Description

Plant Description

"H569-2448"

DC1,DES

Plant Voltage Type

24V or 48V

"24V"

"48V"

DC1,TYP

Automatic Daylight Savings Feature

1=Enabled

0=Disabled

1

PS1,DLS

Display Contrast

0 to 100%

50

PS1,DCT

Temperature Display Units

C or F

"C"

PS1,TUN

Date Format

"MM/DD/YYYY"

PS1,DTF

Time Format

12 or 24

12

PS1,TMF

Front Panel Configuration

1=Enabled

0=Disabled

1

PS1,FPC

Remote rectifier Off

1=Enabled

0=Disabled

0

PS1,RRF

Emergency Power-off Enable

1=Enabled

0=Disabled

1

PS1,POE

User Name Login Enable

1=Enabled

0=Disabled

0

PS1,USR

Front Panel PIN enable

1=Enabled

0=Disabled

0

PS1,FPE

Front Panel Pin Default

Four digits 0-9

"0000"

PS1,FPP

Front Panel PIN timeout

1 to 120 minutes

30

PS1,FPT

Daylight Saving Start

mon:wk:dow:min

mon:-1:dom:min

"3:2:0:120"

PS1,DSS

Daylight Saving End

mon:wk:dow:min

mon:-1:dom:min

"11:1:0:120"

PS1,DSE

Uninstall Equipment Timeout

0 to 60s

15

PS1,UET

Controller Ambient Temperature
High

35 to 75

c

C

75

AMTH1,THR

Controller Ambient Temperature
Low

-40 to 10 C

-40

AMTL1,THR

Critical Equals Major

1=Enabled

0=Disabled

1

PS1,CEM

User Password

"lineage"

PAS U,

Super-user Password

"super-user"

PAS S,

Administrator Password

"administrator"

PAS A,

Low Voltage

Disconnects

Battery Disconnect Control Mode

0=none, 1=voltage

2=voltage/time

1

CN1,DAM

Battery Disconnect 1

Battery Disconnect Time Delay

0 to 300 minutes

0

CN1,DDY

Battery Reconnect Control Mode

0=none, 1=voltage

2=voltage/time

1

CN1,RAM

Battery Reconnect Time Delay

0 to 300 sec

0

CN1,RDY

Battery Disconnect Description

<=32 Chars

"LVBD1"

CN1,DES

Battery Disconnect Open
Description

<=32 Chars

"LVBD1 Open"

CNO1,DES

Battery Disconnect Open Front
Panel Description

<=32 Chars

"LVBD1 Open"

CNO1,FDS

Battery Disconnect Failed
Description

<=32 Chars

"LVBD1 Failed"

CNF1,DES

Battery Disconnect Failed Front
Panel Description

<=32 Chars

"LVBD1 Failed"

CNF1,FDS

Load Disconnect 1

Load 1 Disconnect

1=Enabled

0=Disabled

1

CN2,ENA