Table d-1 standard configuration item defaults – GE Industrial Solutions Pulsar Plus Controller User Manual

Page 173

Advertising
background image

Pulsar Plus Controller Family

Issue 7 December 2011

173

Table D-1 Standard Configuration Item Defaults

Factory Default

Factory 24V

Rectifier

Default

Factory 48V

Rectifier

Default

Category

Description

Range

Factory

Factory 24V

Factory 48V

obj,attr

Load 1 Disconnect Control Mode

0=none, 1=voltage

2=voltage/time

1

CN2,DAM

Load 1 Disconnect Voltage

19.5 to 25V

-39.0 to -50V

21.00

42.00

CN2,DTH

Load 1 Disconnect Time Delay

0 to 300 minutes

0

CN2,DDY

Load 1 Reconnect Control Mode

0=none, 1=voltage

2=voltage/time

1

CN2,RAM

Load 1 Reconnect Voltage

19.5 to 27

-39.0 to -55.0V

22.00

44.00

CN2,RTH

Load 1 Reconnect Time Delay

0 to 300 sec

0

CN2,RDY

Load 1 Disconnect Description

<=32 Chars

"LVLD1"

CN2,DES

Load 1 Disconnect Open Description

<=32 Chars

"LVLD1 Open"

CNO2,DES

Load 1 Disconnect Open Front Panel
Description

<=32 Chars

"LVLD1 Open"

CNO2,FDS

Load 1 Disconnect Failed
Description

<=32 Chars

"LVLD1 Failed"

CNF2,DES

Load 1 Disconnect Failed Front
Panel Description

<=32 Chars

"LVLD1 Failed"

CNF2,FDS

Load Disconnect 2

LV Load 2 Disconnect

1=Enabled

0=Disabled

0

CN3,ENA

LV Load 2 Disconnect Control Mode

0=none, 1=voltage

2=voltage/time

1

CN3,DAM

LV Load 2 Disconnect Voltage

19.5 to 25V

-39.0 to -50V

21.00

42.00

CN3,DTH

LV Load 2 Disconnect Time Delay

0 to 300 minutes

0

CN3,DDY

LV Load 2 Reconnect Control Mode

0=none, 1=voltage

2=voltage/time

1

CN3,RAM

LV Load 2 Reconnect Voltage

19.5 to 27

-39.0 to -55.0V

22.00

44.00

CN3,RTH

LV Load 2 Reconnect Time Delay

0 to 300 sec

0

CN3,RDY

Load 2 Disconnect Description

<=32 Chars

"LVLD2"

CN3,DES

Load 2 Disconnect Open Description

<=32 Chars

"LVLD2 Open"

CNO3,DES

Load 2 Disconnect Open Front Panel
Description

<=32 Chars

"LVLD2 Open"

CNO3,FDS

Load 2 Disconnect Failed
Description

<=32 Chars

"LVLD2 Failed"

CNF3,DES

Load 2 Disconnect Failed Front
Panel Description

<=32 Chars

"LVLD2 Failed"

CNF3,FDS

Load Disconnect 3

Load 3 Disconnect

1=Enabled

0=Disabled

0

CN4,ENA

Load 3 Disconnect Control Mode

0=none, 1=voltage

2=voltage/time

1

CN4,DAM

Load 3 Disconnect Voltage

19.5 to 25V

-39.0 to -50V

21.00

42.00

CN4,DTH

Load 3 Disconnect Time Delay

0 to 300 minutes

0

CN4,DDY

Load 3 Reconnect Control Mode

0=none, 1=voltage

2=voltage/time

1

CN4,RAM

Load 3 Reconnect Voltage

19.5 to 27

-39.0 to -55.0V

22.00

44.00

CN4,RTH

Load 3 Reconnect Time Delay

0 to 300 sec

0

CN4,RDY

Load 3 Disconnect Description

<=32 Chars

"LVLD3"

CN4,DES

Load 3 Disconnect Open Description

<=32 Chars

"LVLD3 Open"

CNO4,DES

Load 3 Disconnect Open Front Panel
Description

<=32 Chars

"LVLD3 Open"

CNO4,FDS

Load 3 Disconnect Failed
Description

<=32 Chars

"LVLD3 Failed"

CNF4,DES

Load 3 Disconnect Failed Front
Panel Description

<=32 Chars

"LVLD3 Failed"

CNF4,FDS