Pulsar Plus Controller Family

Issue 7 December 2011

109

Table 40 QS871 J100 and J101 Signal Description

7

No Connection

8

No Connection


ES772A Remote Distribution Module

Overview

The ES772A allows the controller to communicate with devices in TEPS or OEM distribution panels. It will
allow the controller to alarm for open load and battery protectors, read battery current from an external
shunt, and control a non-latching contactor. The contacts can be assigned as a load-disconnect or as a
battery disconnect.

Figure 21: ES772A Remote Distribution Module

Controls, LED and Connectors
Receptacle J1:
User connections to external distribution module.

Receptacle J3: User connections to external distribution module.

J100/J101: User connections to the controller J10, other devices such as the QS873A VT-Probe and the
ES771A Remote Voltage Monitor Module, and other RJ45 connections carrying the RS485 rectifier
communication bus.

Receptacle J5: User connections to external distribution module.

Mounting Hole MH1: Mounting hole to mount module in user application.

Mounting Hole MH2: Mounting hole to mount module in user application.

LVD2 Disc SW: Disconnect switch for external contactor 2

Manual LVD Cont Connect: Switches for forced reconnect function.

LVD1 Disc SW: Disconnect switch for external contactor 1, when wired as described in installation section.

LED: This is a tri-colored LED and will illuminate accordingly for the conditions shown below.